LG QS G D C'. L.d lj b

~

D Peach Bottou Atomic Power Station (D8Lr B A U_ ld S C f Pl!ILADELPilI A ELF.cTPIC Cot!PA!W Delta. Permsylvanin 17314 Februa ry 11. 1975

'r.

Jamer. P. O'Reilly, Director itfice of Inrpcetion and Enforcement egion i

!ni ted St.tts.4 Nuclear Regulatory Coreission 131 Park Avenue

'iug of Prussia. Pennsylv.Ania 19406 Jubj e c_t :

Abnormal Occurrence _24_-Ito_ur No ti ficat io_n ConfirninG.

J. F. Franz' phone convernation with !!r. L7 alt Daunack. Reginn 1 Nuclent l'egulator'/ Cor:minnion on February ll 1975.

Reference:

License Nunber DPR-44 Technical Specification Reference Tabic 3.2.B Report No. :

$0-277-75-1$

Report Dater February 11. 1975 Occurrence Date:

February 10. 1975 Facility:

Peach Botcom Atomic Power Station R.D. 1. Dc.lta, Pennsylvanic 17314 Identification of Occurrenco:

Setpoint shifr. on dPIS-2-2-138A. Recire. Pump AP 4o LPCI loop selection logic.

Conditionu Prior to Occurrence:

Unit 2 at 90% power.

Description of Occurrence:

During routine instrument surveillance testing, dP15-2-2-138A vao found to trip at 0.9 puid.

The Technical Specification limit is 2 paid +1.

Designation of Apparent Cause of Occurrence:

Setpoint shift.

Analynis of occurrence:

This tainor setpoint shift has minical snicty implications since it is part of a one-of-tvo-twice logic and in also redundant in the other LPCI systen.

Correc tive i.etion:

The ca= follower uns found to be unsaticfactory, repinceit, and properly alir.ned.

The nuitch was recalibrcted and checked for proper calibration per the applicable surveillance test.

Failure Data:

Thir. is the firi:t failure of this type on svitchen in this service.

8401270067 750220

  • 'erv trul" yours.

PDR ADOCK 05000277

. *Y !

S PDR

,MEMW,.

t.

T. Ullrich, Superintendent REGULATORY OPERATIONS 16 > FILE DJPY Peach botton Atotic Power Station