ML20086K371

From kanterella
Jump to navigation Jump to search
Telecopy AO 75-16:on 750212,excessive Leakage Found on HPCI Turbine Exhaust Check Valve 23-65.Cause Under Investigation. Valve Will Be Inspected & Maintained as Required to Achieve Acceptable Leakage Rate
ML20086K371
Person / Time
Site: Peach Bottom 
Issue date: 02/13/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086K355 List:
References
AO-75-16, NUDOCS 8401270049
Download: ML20086K371 (1)


Text

o o..

Y a

  • /

40 CCc.% 4, mu:n PilILADELPHIA ELT.CTRIC COMPANY Peach Bottom istomic Power Station Delta Pennsylvania 17314 February 13, 1975

_r.

James P. O'Reilly, Director

.ifice of Inspection and Enforcement 3rgion 1

.:1ced States Nuclear Regulatory Commission

31 Park Avenue c.cg of Prussia, Pennsylvania 19406 Fubject:

Abnormal Occurrence 24-Hour Notification 2:sfirming W. T. U11 rich's phone conversation with Mr. Walt Baunack, Region 1, Taited States Nuclear Regulatory Concission on Pcbruary 13, 1975.

ieference:

License Number DPR-44 Technical Specification

Reference:

4.7.A.2.f tapert No. :

50-277-75-16

.J_4 port Date:

February 13, 1975 O currence Date:

February 12, 1975 Ta:ility:

Peach Bottom AtomLc Power Station R.D. 1, Delta, Pennsylvania 17314

!dentification of Occurrence:

Exces sive.1. nk a ce..o L IIf.CI.Iurb.ine. E;:haus t_Chn.ck _Yalve_ (- 23-65).

!caditions Prior to Occurrence:

Unit 2 shutdown for piping inspection.

escription of Occurrence:

the HPCI Turbine Exhaust Check Valve, was During a routine local leak rate test, found to leak in excess of 2000 cc/ min.

esignation of Apparent Cause of Occurrence: failure to close tightly is being investigated.

The cause of the check valve's 1

A.=417 sis of Occurrence:

The safety icip11 cations of thin occurrence uro ninical since the inner turbine isolation stop check valve ( 23-12) closed and sealed satisfactorily.

exhaust 2 rrective Action:

The valve wiLL be inspected and maintained as required to achieve an acceptable leakage rate.

Isilure Data None.

Ve ry truly yours.

NW

/.,,4 l

s

- - - -. - -