3 O

O o

PHILADELPHIA ELECTRIC COMPANY

"['

2301 MARKET STREET g}

p g% p-PHILADELPHIA. PA.19101 u.s. gg**'

. u!

2isi 841-4ooo j

s:..; vs, u;a na.*

j w

1 c)

September 20, 1974 Mr. A. Giambusso Deputy Director of Reactor Projects

. United States Atomic Energy Commission Directorate of Licensing Washington, DC 20545

Dear Mr. Giambusso:

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. W. Baunack, A.E.C. Region 1 Regulatory Operations Office on September 11, 1974.

Written notification was made to Mr. James P. O'Reilly, Region 1 Regulatory Operations Office on September 11, 1974.

In accordance with Section 6.7 2.A of the Technical Specifications, Appendix A of DPR-56 for Unit 3 Peach Bottom Atomic Power Station, the following report is being submitted to the Directorate of Licensing as an Abnormal Occurrence.

Reference:

License Number DPR-56, Amendment Number 1 Technical Specification 3 5 0 Report No.:

50-278-74-5 Report Date:

September 20, 1974 Occurrence Date: September 10, 1974 Facility:

Peach Bottom Atomic Power Station R. D. 1, Delta, Pennsylvania 17314 Identification of Occurrence:

Unit 3 Emergency Shutdown Panel RCIC static inverter tripping from operation of the Barometric Condenser Condensate Pump.

Conditions Prior to Occurrence:

The reactor was operating at approximately 22% power with the RCIC in test at the Emergency Shutdown Panc1.

8401240036 740920 9860 PDR ADDCK 05000278

.' COPY SENT REGION __

2

Mr. A. Giambusso Szptember 20, 1974

\\

Page 2 s-Description of Occurrence:

During the test run of the RCIC from the Emergency Shutdown Panel, the static inverter feeding the RCIC flow controller at the Emer-gency Shutdown Panel tripped repeatedly upon automatic starting of the RCIC Barometric Condenser Condensate Pump. Each time, it was immediately reset.

Designation of Apparent Cause of Occurrence:

Investigation points to a failure in the trip circuitry of the particular inverter unit.

i i

Analysis of Occurrence:

(;

r=~rw n w u.w m u--

--.-.~~~.

~.__

?

At the time of the inverter trippings, all other Unit 3 Emer-gency Core Cooling Systems were operable. Due to this, and the short time intervals that the inverter was in a tripped condition, this occurrence has minimal safety significance.

Corrective Action:

~

The inverter unit was replaced with a spare. A storage oscilloscope was installed to monitor inverter input and output during i

the testing. This spare inverter did not trip throughout the remainder of the RCIC testing at the Emergency Shutdown Panel.

The input filter network as outlined in A0-50-277-74-40 is

~

in progress, in that two'of six filters have been installed.

Failure Data:

Five other trippings of RCIC inverters have been reported as:

A0-50-277-74-14, 20, 37, 39, and 40.