i LA 1 ds -d's h' PHILADELPHIA ELECTRI MPANY PGech Bottom Atomic Pow Station w. s./odt s bu.[. *
(
Delta, Pennsylvania w
17314 January 24, 1975 Mr. James P. O'Reilly, Director United States Atomic Energy Commission Directorate of Regulatory Operations 631 Park Avenue King of Prussia, Pennsylvania 19406 Subj ec_t:
Abnormal Occurrence 24-Hour Notification Confirming J. F. Franz' phone conversation with Mr. Tom Shedlovsky, A.E.C. Region i Regulatory Operations Office on January 24, 1975.
Reference:
License Number DPR-56 O
%, \\
f / e.3 Technical Specification
Reference:
Table 3.1.1
'D Report No.:
50-278-75-7 Report Date:
January 24, 1975 g
s/g 3
Occurren*ce Date:
JanuaYy 23,* 1775 ~ '-
%,rg) jy,h '2
' - - * ~ " " ~
9-Facility:
Peach Bottom Atomic Power Station c'
R.D. 1 Delta, Pennsylvania 17314 f,,.h
. D
/
Identification of occurrence:
Failure of the tude switch to consistently initiate a full s'4 p
c moved to the shutdown position.
Conditions Prior to Occurrence:
4 Unfe 3 chutd: :.
Description of Occurrence:
)
After insertion of all rods and placement of the mode switch in SHITTDOW, the mode switch was placed in the P.EFUEL position to enable the movement of a single control rod.
The mode switch failed to allow the motion of a control rod and the svitch was then cycled to the SHUTDOW posf. tion and back to the REFUEL i
position to clear the report.
This time the mode switch failed to initiate a
{
full scram when moved to the SHUTDOW position.
Designation of Apparent Cause of Occurrence:
Intermittent switch contact function.
Analysis of Occurrence:
Because the reactor was shutdown with all control rods inserted, and because the Manual Scram System was operable, the failure of the full scram. capability of the rode. switch in the SHUTDOW position hss ' minimal safety implications..
Corrective Action:
The mode svitch was cycled many tines between SHUIDOW and RIFUEL, and it intermittently failed to initiate full scrams.
is presently being replaced.
Because of this, the mode switch Failure Data:
None.
8401230003 750207 PDR ADOCK 05000278 Very truly yours, S
/gg -
1003 W. T. Ullrich, Superintendent -
Peach Bottom Atomic Power Station