ML20086H575

From kanterella
Jump to navigation Jump to search
AO 75-55:on 750902,drywell Floor Drain Inboard Isolation Valve AO-3-20-82 Failed to Close.Caused by Defective Seat of Solenoid Valve.Solenoid Valve Replaced & AO-3-20-82 Tested Satisfactorily
ML20086H575
Person / Time
Site: Peach Bottom 
Issue date: 09/12/1975
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Boyd R
Office of Nuclear Reactor Regulation
Shared Package
ML20086H578 List:
References
AO-75-55, NUDOCS 8401180032
Download: ML20086H575 (2)


Text

_

g g

d ) D-4iy

^

N PHILADELPHIA ELECTRIC COMPANY R((bf.'!"h'7:

NN

/

2301 MARKET STREET g

SEpyGS[8 :*L

~

~

Es. a' PHILADELPHI A. PA.19101

($

79 12151841-4000

[($'ey

,, g,

  • w g

September 12, 1975 YTrs:'

Mr. Roger S. Boyd, Acting Director Division of Reactor Licensing Office of Nuclear Reactor Regulations United States Nuclear Regulatory Commission Wa shi ng ton, D.C.

20555

Dear Mr. Boyd:

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. Walt Baunack, Region 1, Office of Inspection and Enforcement, United States Nuclear Regulatory Commission on September 3,1975. Wri tten noti fication was made to Mr. James P. 08Reilly, Office of Inspection and Enforcement, Region 1, United States Nuclear Regulatory Coninission on September 3, 1975.

In accordance wi th Section 6.7 2.A of the Technical Specifica-tions, Appendix A of DPR-56 for Unit 3 Peach Bottom Atomic Power S ta ti on, the following report is being submitted to ths Directorate of Reactor Licensing as an Abnormal Occurrence.

Reference:

License Number DPR-56 Technical Specification

Reference:

3.7,0.1 Report No.:

50-278-75-55 Report Date:

September 12, 1975 Occurrence Date:

September 2, 1975 Faci li ty:

Peach Bottom Atomic Power Station R.D. #1, Del ta, Pennsylvania 17314 Identification of Occurrence:

The drywell floor drain inboard isolation valve, A0-3-20-82, failed to close during surveiilance testing.

Conditions Prior to Occurrence:

Hot standby.

Description of Occurrence:

During the performance of a surveillance test, A0-3-20-82 failed to close when given an isolation signal,

/'*Xw 8401100032 750912 PDR ADOCK 05000278 S

PDR

./

pry sgm REGION _

9001

a w..

p 9

Ms. Rogar S. BoyL >

50-278-75-55 September *12, 1975 Page 2

~

Designation of Apparent Cause of Occurrence:

A defective seat of a solenoid valve prevented proper operation of A0-3-20-82.

Analysis of Occurrence:

The safety ' implications of this failure are mininal because the outboard isolation valve did close from the isolation signal.

Corrective Action:

ihe solenoid valve was replaced and A0-3-20-82 was tested satisfactorily.

Failure Data Ac-50-278-74-26 and A0-50-277-74-7 Very truly yours, t

t M.

. Cooney A st. Geni. Supt.

Generation Division cc: Mr. James P. O'Reilly, Di rector, Region 1 Office of Inspection and Enforcement i

Uni ted States Nucicar Regulatory Commission 631 Park Avenue King of Prussia, PA 19046 I

D 9

9

. - e v e 7--

vy w-