Telecopy AO 75-19:on 750331,setpoint of Condenser Low Vacuum Scram Pressure Switch PS-3-5-11A Found Outside Tec Spec Limits.Caused by Setpoint Shift.Pressure Switch Recalibr
ML20086G956
Person / Time
Site: Peach Bottom 
Issue date: 04/01/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086G954 List:
References
AO-75-19, NUDOCS 8401130086
Download: ML20086G956 (1)


Text

_

?

O-O f

C ?' '/* M-PHII/.D12.Pl!!A D.TCIRIC COMTA!.T h.//./M MN Peach Lotton Atomic Power Station 4

Leita, Pecusylvania

'I7314 AprII 1, 1975

~

' Trf. Je.es 7. o'r.e111y, DirecGr Office of Int:pection and Inforcement Region 1 Un i t ed S t a t e s he l ear __ Ke. gu la.t_o. r y Co mi s s..io n

- p Eing of Prussia, Pennsylvania 19406

Subject:

Abr.orm1 Occurren e-24-Nsur Notification Confirring J. F. Franz' phone conve rr.stion wit h Mr.

f..

Brunne$

Region 1 t'nited States Euclear Regulatory Cc:rission on March 31, 1975.

.g-..

~

n6ferencel 1.ieense Nunber'u.,,-55 Technical Specification

Reference:

Table 3.1.1 Report No.:

50-278-75-19

^

Report Dste:

March 31, 1975-Occurrence Date:

lisrch 31, 1975 Facility:

Peach Bottom Atomic Powe Station E.D. 1. Delta, Per.nsylvania 17314 Identificstion of Occurronec:

~ " ~ ~ ' ' '

Setpoint of condenser low vacutes scran precsure switch FS-}-5-11A found to be outside the Technical Specification licit.

Conditions Prior to Occurrences Unit 3 at full pc rer.

Description of Occurrence:

During a routine inservuent surveillance test, PS-3-5-11A was found to trip at 22.4 in. Eg.

na Technical Specificatica limit la greater than or equal to 23 in.

Designation of Apparent Cause of Occurrence:

Cetpoint shift.

i t.nalysis of Occurrence:

The contacts of this device are arranged in a one-out-of-two 'twice trip Icgic.

3 The setpoint of this device, not the trip function, was unsatisfactory. All other devices ronitoring the parncerers of condenser vacuun vere tenediately tested and found t, be operational and correctly calibrated.

h-e ee of the above, this occurrence has minimal safety implications.

Correctivo Action:

The out-of-toter==ce presnure switch ves immediate.ly recalibrated to within the allovable limits of the Tech.ical Specifications and calibration checked in g

acconinnce with the applicable surveillance test.

The other three devices

~

ronitoring the sans variable were tested and found to be satisfactory in both function and setpoint.

Failuro Data:

Seven occurrencen of this type have been previously reperted as: AO-50-277-74-1 A3-50-277-74-19, 40-50-270-74-24,14-50-277-74-35, AD-50-277-74-43, AO-50-277-75-1 an.1 AD-50-277-75-19 Very truly yours, i '

  • - *-+*
  • -s

.i gyu W. T. U11rfch, Superinte~ tut 8401130086 750410 PDR ADOCK 05000278 S