REPORT DATE: November 5, 1974 ABNORMAL OCCURRENCE

' FORT ST. VRAIN NUCLEAR GENERATING STATION PUBLIC SERVICE COMPANY OF COLORADO P. O. BOK 361 PLATTEVILLE. COLORADO 80651 REPORT NO. 50-267/74/19A FINAL IDEITTIFICATION OF OCCL'RRENCE:

As requested in AEC DRO BULLETIN NO. 74-3, Public Service Company of Colorado and General Atomic Company have conducted on inspection of the Class I support structure at Fort St. Vrain.

The results of the inspcetion program indicated that design problems existed on 24 of the'238' Class I support structures at Fort St. Vrain.

f This condition is considered reportable under Paragraph B-3 of AEC DRO Bulletin No. 74-3.

CONDITIONS PRIOR TO 00CL'RRENCE:

Steady State Power Routine Shutdown Hot Shutdown Routine Load Change I

Cold Shutdown Other (specify) l Refueling Shutdown Routine Startup The major plant, para =cters at the time of the ew:nt were as follows:

Power

PTR, O

MWth

ELECT, O

MWe Secondary Coolant Pressure N/A psig

}

Temperature N/A

  • F 8311170102 741114 PDR ADOCK 05000267 S

PDR Flow 0

  1. /hr.

Primary Coolant Pressure O

psig Temperature 100

  • F Corc. Slet 100
  • F Core Atiet
Elow 0

f/hr.

O o.

v. 2 DESCRIPTION OF

' OCCURRENCE:

~

The results of the inspection program of the Class I support structures indicated that a prob 1cm existed regarding the seismic design of some Class I support structures. The problem related to the support structure natural vibrational frequency and the design carthquake vibrational frequency on 24 Class I support structures.

The specific types of support structures found to have problems were:

1.) Heat Exchanger Support Structures 2.)

Filter Support Structures 3.) Varicus Tank Support Structures APPARANT CAUSE OF OCCURRENCE:

X Design Unusual Service Cond.

Including Environ.

Manufacture Component Failure Installation /

Construction Other (specify)

Operator Procedure ANALYSIS OF OCCURRENCE:

The analysis of this problem consisted of a visual inspection of CJ cs: I support structures by General Atomic Company engineers to verify that the field configurcticn was accurately reflected in the seismic calculations; and where incorrect assu=ptions were made, further analysis cnd structural additions were specified.

General Atomic Company elected to'have the Sargent & Lundy Structural Engineering Department perform the additional analysis where required.

CORRECTIVE

-ACTION:

, Additioncl. structural:. steel. bracing.and reinforcement has been added to those structures (24 in all) found to have scis=ic design problems.

The physical work has been co:pleted and scismic calculations have been forwarded to Public Service Company for review.

Public St vice Company is currently in the process of performing an in-dependent review of all calculations and "as-built" configuration for those l

structures requiring additional reinforcement.

i

~

O o

s.. -(

Page 3 During Public Service Company's review of the scismic calculations submitted by General Atomic Company an error was found on one (1) structure calculation regarding an assu=ption made in the General Atomic /Sargent &

General Atomic Company concurred that the error existed, Lundy calculations.

and the additional structural steel bracing indicated has been installed on this support structure.

FAILURE DATA /SIMILIAR REPORTED OCCURRE';CES:

None of the Class I support structures have evidenced any sign of Also, there has not been any similiar reported occurrences actual failure.

at Tort St. Vrain.

-PROGRA301ATIC IMPACT:

None CODE IMPACT:

None Approved by:

Prepared by:

OS-ELt

/)/

/

J1 N

Fr'ederic E. Swart

'~

~

J II.' Reader SherintendentNuclearProduction Resident Engince.