Amends 100 & 89 to Licenses NPF-10 & NPF-15,respectively, Deleting Refs to Movable in-core Detector Sys from TS 3.3.3.2, In-Core Detectors & TS 3/4.8.4, Electrical Equipment Protection Devices, Table 3.8-1
ML20085K393
Person / Time
Site: San Onofre  
Issue date: 10/09/1991
From: Quay T
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20085K396 List:
References
NUDOCS 9110310060
Download: ML20085K393 (10)


Text

- - _ _ _ - _ _ _ _ _ _

l

/pe ts cqo, e\\

i'

  • UNITED STATES

' N.

3

- S NUCLEAR REGULATORY COMMISSION

'oj j

WASHINGTON. o.C. 20666 g %>....f SOUTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY THE CITY OF RIVERSIDE. CALIFORNIA THE CITY OF ANAHEIM. CALIF 0RNE DOCFEY NO. 50-361 SAN ONOFRE NUCLEAR GENERATING STATION. UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amndment No.100 License No. NPF-10 1.

The Nuclear Regv' gry Comission (the Comissiori) has found that:

A.

The app (lication for amendment ey Southern Califemia Edison Company, et al.

SCE or the licensee), dated August 16, 1991, complies with the standards and requirements of the Atomic Energy Act of 1954, as anended (the Act), and the Comission's regalations set forth in 10 CFR Chapter it B.

The f acility will operate it, confomity with the applicaticn, the provisions of the Act, and the rules and regulationc of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be cor. ducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not ba inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amenckent is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

9110010060 91100'?

ADOCK0500gl DR

~

2-l 2.

Accordingly, the license is arended by changes to the Technical Spect.

fications as indicated in the attachment to this license avendment, and paragraph 2.C(2)ofFacilit asended to read as follows:y Operating License No. NpT-10 is hereby (2) _ Technical Specifications The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revise:

through Amendment No.100 are hereby incorporated in the license.

Southern California Edison, Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license anendment is effective as of the date of its issuence and must be fully inplemented no later than 30 days from the date of issuance.

FOR THE NUCLEAR REGULATORY C0m!S$10N vtbw h W').

Theodore R. Quay, Director ProjectDirectorateV Division of Reactor Projects !!!/IV/V i

Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: October 9, 1991 l

l l

l l -.

I r

t P

p m-c g-e 1,.-,r

.m,-6 v

-e

.,,,,----..re-,,

+m-=--

m -.

  • -m

. =. -.. -. _ - -.. - - _..

e ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO.100 TO FACILITY OPERATING LICENSE NO. NPF-10 DOCKET NO. 50-361 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enc _losed pages.

The revised pages are identified by the captioned amendment number and contain marginal lines indicating the areas of change.

The corresponding overleaf pages are also provided to maintain document completeness.

REMOVE INSERT 3/4 3-41 3/4 3-41 3/4 8-19 3/4 8-19 9

9 l

.,,...-,,--..,.-,.,~...,,_n

INSTRUMENTATION INCORE DETECTORS LIMITING CONDITION F"9 OPERATION 3.3.7.2 The incore detection system shall be OPERABLE with:

At least 75% of all incure detector locations, and a.

b.

A minimum of two quadrant symmetric incore detector locations per core quadrant.

An OPERABLE incore detector location shall consist of a fuel assembly containing a fixed detector string with a minimum of four OPERABLE rhodium l

detectors.

i APPLICABILITY:

When the incore detection system is used for monitoring:

a.

AZIMUTHAL POWER TILT.

b.

Radial Peaking Factors, c.

Local Power Density, d.

DNB Margin.

ACTION:

With the incore detection system inoperable, do not use the system for the above applicable monitoring or calibration functions.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.3.3.2 The incort detection system shall be demonstrated OPERABLE:

By performance of a CHANNEL CHECK within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> prior to its use if a.

7 or more days have elesped since the previous check and at least once per 7 days thereafter when required for monitoring the AZIMUTHAL POWER TILT, radial peaking factors, local power density or DNB margin:

b.

At least once oer 18 months by performance of a CHANNEL CALIBRATION operation whici exempts the neutron detectors but includes all electronic components.

The neutron detectors shall be calibrated prior to installation in the reactor core.

SAN ONOFRE-UNIT 2 3/4 3-41 AMENDMENT NO. 100

m R

TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

=

Primary Device

~

Back.up Device y

Number Number Service Description N

2BA04 2BLP0802 (2BA04-B)

CEDM Cooling Supply Fan E-4038 2BA04 (Enclosure Heater) 2BLP0814 (2BA04-C)

Standby Containment Normal Cooling Fan E-393 2BA04 (Enclosure Heater) 2BLP0826 (2BA04-D)

Containant Normal Cooling Fan E-394 2BA04 (Enclosure Heater) 2BLP0828 (2BA04-E)

Containment Normal Cooling Fan E-397 2BA11 w

2BLP0905 1

2BA25 Cont. Structure Electric Heater E-467 2BLP0910 2BA26 Cont. Cooling Unit E-393 Cire. Water Outlet HV-9940FB 2BLP0911 a,

g 2BA27 Cont. Cooling Unit E-394 Cire. Water Uutlet HV-9940EB 2BLP0912 Cont. Cooling Unit E-397 Cire. Water Outlet HV-9940DB 2BA31 2BLP0913 Cont. Cooling Unit E-393 Cire. Water Outlet HV-9940FC 2BA32 2BLP0914 2BA33 Cont. Cooling Unit E-3'.A Cire. Water Inlet HV-9940EC 2BLP0915 Cont. Cooling Unit E-397 Circ. Water Inlet HV-99400C 2BA3G 2BLP0808 2BA37 RCP 1A Oil Lift Pump 1A1 P-260 2BLF0B09 RCP IB Oil Lift Pump 181 P-264 2BA38 2BLP0810 2BA39 RCP 2B Oil Lift Pump 231 P-262 2BLP0301 2BA40 Reactor Coolant Drain Pug (W) P-023 2BLPOB11 2BA41 RCP 2A Oil lift Pump 2A1 r-266 2BLP0817 2BA42 HCP 1A Anti Rev. Rotatien Device tube Pump 1 P-399 g

2BLP0818 RCP 2B Anti Rev. Rotation Device Lube Pump 1 P-401 2BA43 2BLP0019 5

2BA44 RCP IB Anti Rev. Rotation Device tube Pump 1 P-403 2BLP0820 5

2BA45 RCP 2A Anti Rev. Rotation Device Lube Punp 1 P-405 2BLP0902 2BA46 Reactor Cavity Cooling Fan A-319 2BLP0903 2P Standby Reactor Cavity Cooling Fan A-321

~

8

, p uog 3"

UNITED STATES

  • i $

NUCLEAR REGULATORY COMMISSION o

WASHINGTON, D.C. 200ti6

,/

%,i v 50tlTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY THE CITY OF RIVERSIDE, CALIFORNIA g r.ITY OF ANAHEIM, CALIFORNIA DOCKET NO. 50-362 SAN ONOFRE NUCLEAR GENERATING STATION, UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 89 License No. NPF-15 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The app (lication for amendment by Southern California Edison Crpany, et al.

SCE or the licensee), dated August 16, 1991, co.cplies m.h the standards and requiremer.ts of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth ja 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (t) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the connon defense and security or to the health ar.d safety of the public; and 7.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Cumission's regulations and all applicable requirements have been satisfied.

i 2.

Accordingly, the license is amended b; changes to the Technical Spect-fications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-15 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised th'ough Amendment No. 89, are hereby incorporated in the license.

Southern California Edison Coegauy shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance and must be fully implemented no later 'han 30 days from the date of issuance.

FOP. THE NUCLEAR REGULATORY COMMIS510N llh h

").

Theodore R. Quay, Director Project Directorate V Division of Reactor Projects Ill/IV/V Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technica?

Specifications

~

Date of Issuance: October 9, 1991

.. =

-.4 ATTACINENT-TO LICENSE AMENDMENT AMENDMENT NO. 89 TO FACILITY OPERATING LICENSE NO. NPF-15 DOCKET NO. 50-362 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and contain marginal lines indicating the areas of' change. The corresponding overleaf pages are also provided to maintain document corrpleteness.

EEMOVE INSERT 3/4 3-41 3/4 3-41 3/4 8-19 3/4 8-19 L

l-t J

I

t INSTRUMENTATION INCORE DETECTORS LIMITING CONDITION FOR OPERATION 3.3.3.2 The incore detection system shall '

OPERABLE with:

At least 75% of all incore detectu locations, and a.

b.

A minimum of two quadrant symmetric incore detector locations per core quadrar.t.

An OPERABLE incore detector location shall consist of a fuel assembly containing a fixed detector string with a minimum of four OPERABLE rhodium detectors.

APPLICABILITY: When the incore detection system is used for monitoring:

a.

AZIMUTHAL POWER TILT, b.

Radial Peaking Factors, c.

Local Power Density, d.

DNB Margin.

ACTION:

With the incore detection system inoperable, do not use the system for the above applicable monitoring or calibration functions.

The provisions of Specifications 3.0.3 and 3.0.a are r.ot applicable.

SURVEILLANCE REQUIREMENTS 4.3.3.2 The incore detection system shall be demonstrated OPERABLE:

By performance of a CHANNEL CHECK within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> prior te its use if a.

7 or more days have elapsed since the previous cht.ck 6nd at least once per 7 days thereafter when required for nionitoring the AZIMUTHAL POWER TILT, radial p-aking factors, local power density or DNB margin:

b.

At least once aer 18 months by performance of a CHANNEL CALIBRATION operation whici exempts the neutron detectors but includes all electronic components. The neutron detectors shall be calibrated prior to installation in the reacter core.

SAN ONOFRE - UNIT 5 3/4 3-41 AMENDMENT NO. 89

y TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

~

x%5 Primarv Device Backup Device Humber Number Service Description e

3 3BA04 3BLP0802 CEOM Cooling Supply Fan E-403B (3BA04-B)

(Enclosure Heater) w 3BA04 3BLP0814 Standby Containment Normal Cooling Fan E-393 (3BA04-C)

(Enclosure Heater) 3BA04 3BLP0826 Containant Normal Coo 11r.g Fan E-394 (3BA04-0)

(Enclosure Heater) 3BA04 3BLP0828 Containment Nomal Cooling Fan E-397 (3BA04-E) 3BA11 3BLP0905 Cont. Structure Electric Heater E-467 3BA25 3BLP0910 Cont. Cooling Unit E-333 Cire. Water Outlet HV-9940FB mg 3BA26 3BLP0911 Cont. Cooling Unit E-394 Cire. Water Outlet HV-9940EB 3BA27 3BLP0912 Cont. Cooling Unit E-397 Cire. Water Outlet HV-9940D8 b

3BA31 3BLP0913 Cont. Cooling Unit E-393 Cire. Water fiutlet HV-9940FC 3BA32 3BLP0914 Cont. Cooling Unit E-394 Circ. Water Inlet HV-9940EC 3BA33 3BLP0915 Cont. Cooling Unit E-397 Cire. Water Inlet HV-9940DC 3BA36 3BLP0808 RCP 1A 011 Lift Pump 1A1 P-260 3BA37 3BLP0809 RCP 18 011 Lift Pump 181 P-264 3BA38 3BLP0810 RCP 28 011 Lift Pump 281 P-262 3BA39 3BLP0901 Reactor Coolant Drain Pump (W) P-023 3BA40 3BLP0811 RCP 2A 011 Lift Pump 2A1 P-266 3BA41 3BLP0817 RCP 1A Anti Rev. Rotation Device tube Pump 1 P-399 3BA42 3BLP0818 RCP 29 Anti Eev. Rotation Device Lube Pump 1 P-401 E

3BA43 3BLP0819 RCP 18 Anti Rev. Rotation Device tube Pump 1 P-403 E

3BA44 3BLP0820 RCP 2A Anti Rev. Rotation Device Lube Pump 1 P- 05 SE 3BA45 3BLP0902 Reactor Cavity Cooling Fan A-319 3

3BA46 3BLP0903 Standby Reactor Cavity Cooling Fan A-321 2

.