ML20085C939

From kanterella
Jump to navigation Jump to search
Telecopy Ao:Average Power Range Monitor Reference Flows Found Approx 7% Greater than Indicated % of Rated Core Flow. Check of Drive Flow Transmitter Calibr to Be Performed
ML20085C939
Person / Time
Site: Quad Cities 
Issue date: 10/25/1974
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20085C937 List:
References
NJK-74-348, NUDOCS 8307130252
Download: ML20085C939 (1)


Text

. _ _ _ _

  • Cr_ - ^_ :-?. Edison

~

Cuad.

Nuclear Pcher Station

.fi

~ Post Box'216

. 1 COrdova Hlinoi361242 g3 Torephorte309/664 2241

%T. Km74-348 Telecopy

. Region III,. Attentions

-Mr. C. FeiArabend October 25, -1974 J. Keppler,. Regional'. Director

'Directorateaof. Regulatory Operations

/ Region III U.S. Atomic. Energy Ccenniasion 799 Rooseveit 1 Road Glen Ellyn, Illinois 60137

Reference:

Quad-Citics Nucinar Power Station, : Unit 2, Docket No.

50-265..DPR-30, Appendix A, Sections 1. 0. A.1, 2.1. A.1, 6.6.B.1.a.

Dear Mr..'Keppler:

The purpose of this letter is to provide you with notification.of

.an Abnormal occurrence as required by Technical specification

-6.'6.B.1.a swithin"24. hours of the occurrenco.

The Unit.2 APRM-RBM reference flows.were found to be.approximately 7$ greater than the indicated percent.of rated -core flow.

A core flow calibration' verified the accuracy of the indicated core flow.

. A check.of the. drive flow transmitter calibrations, which requires 1/2...soram, will..be performed at the earliest. opportunity.

.In

.athe interim, the, gains of the total edrive flow proportional.ampli-fiers (2"260-BA and B) chave been adjusted so that the. APRM refer-ence. flows correspond to the ' core flow.

This lends the required

. conservatism to the flow biased trip settings until further in-vestigation determines the :cause of the instrument drift.

This. occurrence was discussed ;by telephone with Mr.. Jordan of your office on October :25,1974.

Further ~information.will be. pro-l vided by. Abnormal Occurrence 1 Report AO S0-265/74-26.which will be ' submitted..within 10. days.cof the -date :of ~.this. occurrence.