ML20085C902

From kanterella
Jump to navigation Jump to search
Telecopy Ao:On 740929,diesel Generator 1/2 Failed to Start. Caused by Both Air Valves Being Closed at Receiver Outlet. Locks Will Be Provided for Generators Air Receiver Outlet Valves & shut-off Valve to Air Start Motor
ML20085C902
Person / Time
Site: Quad Cities  
Issue date: 09/30/1974
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20085C901 List:
References
NJK-74-303, NUDOCS 8307130195
Download: ML20085C902 (1)


Text

[$3h CommofNalth Edison J ~

eN sbaeratina Station I (@C D) 0:an.cita 5-p:-%.

Post OfficeTiox 21G 4(f M %

t

'hy? Cordova.1:1. nom r1242 k f.kA tr

p lerophonc300/654 2241

/

s

' Q:t< /g[lb,$

I flJK-74-303 Telecopy: Region *III, Attention: fir. C. Feicrabend 39 b Nh f'i ta.

7e g

E.

l September 30, 1974 93/

IT.

J. Keptiler, Regional Director Directorate of Regulatory Operat inns fic9 on 111 I

U. S. Atomic Energy Commission 799 Roosevelt Road C!cn Ellyn, Illinois 60137

Reference:

Quad-Cities t!uclear Pcwer Station, Unit One/Two, Docket No.

50-265, 50-254, DPR-30, 29, Appendix A, Sections 1.0.A.4, 4.9.A.I.b, 6.6.B.l.

Dear fir. Keppler:

The purpose of this letter is to provide y'ou with notification of an Abnormal Occurrence as required by Technical Specification 6.6,0. la within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of the occurrence.

At 1200 hours0.0139 days <br />0.333 hours <br />0.00198 weeks <br />4.566e-4 months <br /> on Septen.ber 29, 1974, with Unit One running at 610 cnd Uni t Two at 306 l4Ve, 1/2 diesel generator failed to start due to both air valves being closed at the receiver outlet. The dicscl generator was started immediately upon the opening of both air valves and a monthly operability test conducted satisfactory. Diesel generators I and 2 air system was checked and found to be in proper condition.

"S" locks will be provided for all three diesel generator's air receiver outlet valves and shut-off valve to the air start notor.

This occurrence was discussed by telephone with Mr. Feierebend of your of fice on Sept. 30, 1974 Further information will be provided by Abnormal Occurrence licport A0 50-254/74-31 which wi11 be submitted within 10 days of the date of this occurrence.

Very truly yours, COMM0!1 WEALTH EDISON C0llPANY QUAD-CITI ES hUCLEAR POWER, STATION

.i / /

/

f t) y0, f.f.l% tst,

N. J. Kallvianakis Station Superintendent n r.

HJK/LDR/saa cc:

Directorate of Licensing g.JV5; 99{I J. S. Abcl 8307130195 741009' Sl[6' gDR ADOCK 05000 M g

I COPY SENf REGION Is s