Text
~
Ctmm:nh.th Edis:n
)
,A
'C.g Cuad Citicshc6eratino 5tation I
Po;t Off.ce Box 216 ~
1
'h6 Cordova, litinois 61242 Telephone 309/6S4 2241 NJK-75-140 March 18, 1975 i'
1 J. Keppler, Regional Director Directorate of Regulatory Operatlons Region ill U. S. Nuclear Regulatory Commission 799 Roosevelt Road l
Glen Ellyn, IL 60137
Dear Mr. Keppler:
The purpose of this letter is to provide you with a current status report concerning Abnormal Occurrence Report A0 50-265/74-32 On December 26 and 27,1974, Unit Two main steam isolation valves (MSIVs) were leak rate tested. The following results were reported.
Within Leak Rate Limitations: MSIVs 2-203-lC, 2-203-ID and 2-203-20 Exceeded Leak Rate Limitations: MSIVs 2-203-1A, 2-203-IB and 2-203-2C.
Due to water leakage through the inboard MSIVs 2-203-1A and 2-203-1B, an accurate numerical leak rate value could not be determined for the respec-tive outboard MSIVs 2-203-2A and 2-203-28.
MSIVs 2-203-lA, 2-203-1B and 2-203-2C were subsequently cleaned and tapped.
On March 10, 1975, the following leak rate test results were determined.
MSiv LEAKAGE
- LEST STATUS _
- 1. 2-203-IA 259.0 Did Not Pass 2-203-2A
- 2. 2-203-1B 0.0 Pass j
2-203-2B i
- 3. 2-203-IC 8.65 SCFH Pass 2-203-2C On March 14, 1975, MSIV 2-203-2A was determined to have leakage in excess of the Technical Specification limit of 11.5 SCFH. A0 50-265/75-9 will describe the details necessary to correct MSIV 2-203-2A. This report will be submltted at a later date when the work is completed.
Combined leakage of the inboard MSIV and its respective outboard MStV.
O pg S
L F: ui c
O o
. March 18, 1975 J. Keppler l
l 1
Sincerely.yours, COMMONWEALTH EDISON COMPANY QUAD-CITIES NUCLEAR POWER STATION b-
'M N. J. Kallvianakis g,
Station Superintendent NJK:PC/dkp i<
cc:
Directorate of Licensing ll J. S. Abel e
-i t
l' i.
p.
r
.e
~ll x
' J ':
1~
l i
I e
s$
, + -
- - -.