Cosummmve Edloon
~-
f;
, ocas.cmes
.mogsuman 4
Post Oct.ca Gax216 4
-,/ consova, minots 61242' Telephone 309/654 2241" NJK-75-253 704ecopy:
Region _ t II:, Attention:- Mks Clarence. FeIerabend.
Itay-S 1975 J. Keppler, RegiorisF Director Dirsetorate, of, Regulatory Operations -
R gion IlI-U'. S. Nuclear Regulatory-Ccmnissioer.
799 Roosevelt Road-Glan: Ellyn3 i l I.Inci s 60137-Refarencer quad-Cities Nuclear Power Station, Unit i Docket No. 50-254, DPR-29:
Appendix A. Sections 1.O s A.2,. 3.3.D.1., 6.6.B'. i.a.
Denr Mr. Keppler:-
The purpose of this. Ietter is to-provide you wi t h> noti ficiatlon. of an-Abnormal Occurrence as required by Technical Specification 6 6.8.1..a within. 24' hours of-the occurrence.
l At 10400 a.m. on May-2, 1975. with-the Uni t in, refuel mode,. rod J-13. was wi thdrawn i
from position 00 to..48-for control rod drive.m Intenance.
A simulated full in-signal was inserted to. alicw: another rod to be-withdrawn for control rod drive maintenance.
At. 8:3i a.m. on nay 3,1975, rod J-15 was withdrawn from post tion.
00 to 4Bi At. 6 :25-p.m.,
while. attempting to withdraw J-IS for a coupling check.
folloedng naintenance, it was discovered that J-13 was still withdrawn.
Thus,.
two rods had licen withdrcwn within the scre nine rod array, in violation of.
Technical Specification 3.3 0.I.
Rod J-13 was th:n Inserted, and the coupiing check on J-15 was successfully co@leted.
A procedural review is being conducted to-determine the actions necessary to. pre-vant similar future occurrences.
This occurrence was discussed by telephone with.itr. Clarence Feierabend of your offi'ce on May 4,1975 Further Information will be provided by Abnormal Occurrence R: port AO' So-254/75-10rwhich.wii1: be submitted within 10 days of the date of this.
occurrence.
- V;ry truly yours, Comt0 WEALTH ED tSOH' COMPANY QUAD-CITIES lit! CLEAR PO',IER STATIO'N N.. J. Kalivianskis-8306170330 750513 Station' Superintenden PDR ADOCK 05000254 S
PDR NJK/Ci!S/Jeh cca ' D Trectorate of. Licensing J. 5. Abel
\\c 97%c
.