ML20084S753

From kanterella
Jump to navigation Jump to search
AO 50-265/75-18:on 750522,single Valve Failure Made Standby Gas Treatment Sys Inoperable.Caused by Design Deficiency. Mod Request Has Been Initiated
ML20084S753
Person / Time
Site: Quad Cities 
Issue date: 06/20/1975
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20084S754 List:
References
AO-50-265-75-18, NJK-75-328, NUDOCS 8306170227
Download: ML20084S753 (2)


Text

i Commonwealth Edison

{

Ouad-Cres Nuclear Power Station i.

Post O( j:nois 61242.

ox 216 Cordovas

~ =

="

-4 Tc!cphone 309/654 2241 4*

.I TI,h'.]s..,

4 sY Il y N. Gt ] !,'?,

NJK-75-328

,1'(-

.7 sWG1975..

j 4

June 20,_1975 9

Director of Office of Nuclear Reactor Regulation 1

U. S. Nuclear Regulatory Conmission Washington, D. C. 20555

Reference:

Quad-Ci ties Nuclear Power Station i'

Docket No.60-265, DPR-30, Unit 2 Appendix A, Sections 1.0.A.4, 3.7.B.1, 6.6.B.2.b Abnormal Occurrence Report No. 50-265/75-18 4

The purpose of this letter is to provide you with details concerning an un-3 usual event which occurred at quad-Cities Nuclear Power Station, Unit 2, on May 22, 1975 This report is being :,ubmi tted in accordance with the requi re-ments of Technical Specification 6.6.B.2.b.

Circumstances leading to the discovery of this event were reported to you on May 30, 1975 in Quad-Cities Nuclear Power Station Abnormai Occurrence Report No. 50-265/75-18.

Very truly yours, i

COMMONWEALTH EDISON COMPANY QUAD-ClTIES NUCLEAR POWER STATION f/}

%N 76/

N. J. Kalivicnakis Station Superintendent i

i I

l.

NJK/RAR/lk cc:. Region lII, Directorate of Regulatory Operations J. S. Abel 4

f E

i 1.?

L j

8306170227 750620 gDRADOCK 05000265 PDR_

t.

f

p r

V V

,e' REPORT NUMBER: Unusual Event Letter REPORT DATE: June 21, 1975 EVENT DALE: May 22, 1975 FACILITY: Quad-Ci ties Nuclear Power Station Cordova, 111. 61242 IDENTI FI CATION OF EVENT:

A single valve failure made the Standby Gas Treatment system inoperable.

CONDITIONS PRIOR TO EVENT:

Unit one was at 670 MWe and increasing at the rate of 3 MWe per hour.

Unit two was at 495 MWe and increasing at the rate of 20 MWe per hour.

DESCRIPTION OF EVENT:

On May 22, 1975 a condition involving a single failure of a SBGT system inlet valve was discovered which could result in the loss of the capability of this system to perform i ts safety function.

As the logic for the system is presently designed, an auto initiation signal for one uni t automatically closes the inlet valve to the SBGT system f rom the other unit.

If a failure occurs on the inlet valve for the unit that auto initiates, the condition is such that no inlet valve at all is open to the system.

This is a vio-lation of the " single failure" criteria for the SBGT system.

DESIGNATION OF APPARENT CAUSE OF EVENT:

Design Deficiency Due to a design deficiency, the SBGT system will not remain operable under all conditions with a single component failure.

_ ANALYSIS OF EVENT :

There are no safety implications from the event.

Due to a previous abnormal occurrence both inlet valves have been taken out of service in the open direction and the conditions described above will not affect SBGT system operability.

CORRECTIVE ACTION:

A modifice-request has been initiated and routed to the Station Nuclear Engineerir separtment.

The modi fication request should result in a revision to the present logic scheme to preclude the possibility that a failure similar to that described above would render the system inoperable.

Until the time that the modification is implemented, the inlet valves will remain positioned as described above.