Q.,.
-. ~ -.
9 o
N1AGARA McH AwK POWE R CORPORATION c:
-c
] sowAwe y ?l d
w can4 v ::
7.
aco une couuue wcn
- e.,
w.cusc.n v moi I
ffarch 6, 1970 b
d M
p.
l,q.- Q u
P, l
C
[5 N!
~
Dr. Peter A. T! orris, Director Division of Ileactor Licensing l
United States Atomic Energy Comission b'ashi ng ton, D. C.
20545
Dear Dr. Morris:
{
Subject:
Provisional Operating License DPit-17 Docket 50-220 This is to notify you of a situation in which we exceeded the Technical Speci-fications for Nine !!ile Point.
d[1" +
On February 26, 1970, a batch of radioactive waste was accidentally pumped out 3
- at a flow rate which resulted in an instantaneous concentration of 1.32 x 10-6 pCi/m1 gross beta in our effluent.
This condition existed for approximately A' [ l, 115 hours0.00133 days <br />0.0319 hours <br />1.901455e-4 weeks <br />4.37575e-5 months <br />.
f 'this situation occuried because a mistake was made in interpreting the graph l wbich is part of the waste discharge procedures.
In addition, the hi-hi olarm 1 on the waste discharge monitor was not noticed.
This occurred because waste was being discharged on an almost continuous basis on February 26 and most of this waste exceeded the hi alarm point (1 x 10-7 pCi/ml).
When the hi alarm is in and the annunciator is acknowledged, an increase to the hi-hi alarn (1 x 10-6 pCl/ml) does not give another audible annunciator alarm.
5 The fact that the waste discharge in excess of the Technical Specifications had taken place was detected on a routine audit of the waste records on March 4, 1970. This discharge resulted in a daily average activity of 2.01 x 10-7 pCi/ml in the effluent.
The monthly average activity in the effluent was 3.06 x-10-8 pC1/ml, and the running 52-week average activity was 1.92 x 10-8 pCi/ml at the end of February 26.
. J.d Although no specific analysis was made on this tank, the specific analyses on p#;
- typical waste samples have been running quite consistent.
Based on these 1
p,-
typical analyses, this discharge would consist of 5.4 x 10-7 uCi/ml Co-58,
~*
1.8 x 10-7 pC1/nl Co-60, 2.27'x 10-6 pCi/ml Cr-51, 8.4 x 10-7 pC1/ml Mn-54, p~.3' '
y 1
5.2 x 10-7 pCi/ml Fe-59.
'the. total activity (1.32 x 10-6 pCi/ml gross beta) does not exceed any of the MPC's for these nuclides.
N845//o/74 saos:4o717 7003o6 PDR ADOCK o5000220 S
i pyg OW COPY: SENT REGION
~J' ggg i o 1970
- 00722 721
1 4.
O
\\
\\
le r. Pe t e r.\\. : L u r i r,, Di t eet or Pilj;e 2 f:.t rch 6, 197t)
To prevent a reo';currence, s.o have
- c. v ie,.ul t he 1 aste discharge procedure wit h all the Station Shif't Sun reit arr im ! are raaling a revision to the naste dis-chaq e monitor:
so that t h, hi-hi alnin niuu'nc i:itor ale c.
sill give an additional audible Very truly yours, st 1
.J. Schneider
\\' ice President - Operations inj s I