Ao:On 721217,standby Liquid Control Sys Storage Tank Level Observed to Be High Following High/Low Level Alarm.Caused by Incorrectly Calibr Tank Vol.Sight Glass to Be Installed to Allow Level Determination
ML20084J522
Person / Time
Site: Quad Cities  
Issue date: 01/09/1973
From: Stephenson B
COMMONWEALTH EDISON CO.
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20084J520 List:
References
BBS-73-7, NUDOCS 8305130348
Download: ML20084J522 (3)


Text

r S$.

Commo

lth Edinn (V

/N Ouad-Citi ick ar Power Station

  • [/

Port Oftce box 210 e

AgC'2/

Cordova,l!hnois 01242 O

Telephone 309/654-2241 d.Q,'7 Q.

DDs-73-7 4/ ~

,'\\..

2-h+g> [pk=

1( -

,o g,h.3 January 9, 1973 Q

-9y 46

/

o 7

p Hr. Angelo Giambusso Y (L Deputy Director for Reactor Projects Directorate of Licensing U. S. Atomic Energy Commission Washington, D. C.

20545

Reference:

quad-Cities Nuc1 car Power Station, Unit 2 Docket No. 50-265, License DPR-30 Dear Mr. Glambusso The purpose of this letter is to inform you of the details concerning an abnormality in the sodium pentaborate solution Icvel in the Unit 2 Standby Liquid Control System storage tank.

This was reported to you by telegram on December 22, 1972 as an abnormal occurrence. A review of the level Instrumentation calibration has shown that the minimum required level of 3,470 gallons was not exceeded as initially reported. The ninimum volume / concentration, however, may not have been satisfied after the initial low level was increased by adding water.

On December 17, 1972 with the Unit 2 reactor operating at 80 per cent power a "lligh/ Low Level" alarm was received on the fj' 7' standby liquid control tank at 11:45 a.m.

Indication on the

/r M k' 902-5 penel showed the tank Icvel to be high. Operating

- p personnel then discovered that the air flow through the bubbler leval indicating device was near zero. When this air flow was TI increased rapidly and then set correccly at 1.0 scfh, the tank pW-level Indicated 68 per cent. Apparently the cold air in the bubbler pipe is causing o local crystallization of the boron N3' solution and restricting flow in the tube. This restriction causes a high back pressure and creates a false high level Indication. This effect has been observed before to a lesser extent and has been corrected by periodically blowing out the bubbler tube.

The 68 per cent Icvel in the tank was initially evaluated to be 3,570 gallons. This was based on a volume of 5,250 gallons for the tank at 100 per cent. The solution concentration was greater than 13.4 per cent based on the last sample. Therefore, the decision was made to increase the tank level to 84 per cent and 1

0305130348 730306 gDRADOCK05000$

COPY SENT REGION '

s.,

,r*

L[

y m

j

r

'"4 o

O r

a Mr. Angelo Giambusso January 9, 1973 sample again. At 12:55 a.m. cn December 18, the tank con-centration was found to be 10 95 per cent by analysis. Be-lieving that the solution volume was 4,',10 gallons (84 per cent of 5,250) the volume / concentration requirement of Technical Specification 3.4.C was assumed to be met. On '

December 18, 1972 boric acid and borax were added to increase the tank concentration to 12.36 per cent.

The preliminary review of the incident revealed that 5,250 gallons for 100 per cent was incorrect. Station procedures included an information note that the 72 per cent low level alarm is equivalent to 3,650 gallons which would correspond to about 3,450 gallons at 68 per cent. When the actual calibration on the Instrument was checked, It was found that the transmitter was not calibrated over the real usable volume of the tank as believed. The instrument zero was 6 inches above the bottom of the tank or 2-3/4 inches above the bottom of the pump suction line. The 100 per cent span of the instrument was equal to 130.2 inches of solution.

This data fixes the 68 per cent Indicated tank Icvel at 94.5 inches above the tank bottom whl.:h is a gross volume of 3,715 gallons. The volume of solution below the pump suction which is not usable is 128 gallons; therefore, the net volume was 3,587 gallons indicated.

Applying the actual instrument zero and span to the 84 per cent level and 10.95 per cent concentration yields a net volume of 4390 gallon 3 This would be approximately 10 gallons less than the minimum required for a 10.95 per cent solution.

Having a solution volume approximately 10 gallons less than required is not considered to be of major safety significance -

^

since a 25 per cent margin provided to allow for imperfect mixing is available. Also considering the accuracy of the level Indicating system, the "out of spec" level could have been anywhere from 4330 to 4450 gallons.

With regard to the lost volume in the storage tank, a review-of the records indicated that a drop of about 8 per cent or 400 gallons had occurred over the past 3 months. During this period samples were taken twice a month to monitor the con-centration instead of monthly since the volume was changing.

The corrective action to prevent a recurrence is directed at the level Indication system. As an interim measure the bubbler will be blown out at each time a tank sample is obtained to L

4 4

L o

O

~

Mr. Angelo Giambusso January 9, 1973 prevent a crystal butIdup. The instrument calibration and operating procedures are also being revised to reflect the true usable volume between the pump suction and the overflow pipe. As a permanent corrective action a modification is,being initated to install a sight glass which will allow level determination with an accuracy of less than 10 gallons.

Very truly yours, COMMONWEALTH EDISON COMPANY Quad-Cities Nuclear Power Station p-

. hffbf B. B. Stephenson Superintendent BBS/zm 4