Ao:On 730215,during Calibr,Setpoint of dPIS-1-2353 Found Greater than Tech Spec Limit.Decrease in Setpoint Being Reviewed
ML20084J262
Person / Time
Site: Quad Cities 
Issue date: 02/26/1973
From: Stephenson B
COMMONWEALTH EDISON CO.
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20084J247 List:
References
BBS-73-32, NUDOCS 8305120286
Download: ML20084J262 (1)


Text

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Com e:lth Edison

('

Quad-Cn.cs Nucint Pow:r St tion Post Office Box 216 Cordova, Illinois 61242 Telephone 309/654-2241

's

. t!

N'

~f-v

,6) j%

BBS-73-32 s

dp 4%

p

& N k' %,. %

i February 26, 1973 N

gJ J

Y o>il tcos Mr. Angelo Giambusso Deputy Director of Reactor Projects Directorate of Licensing U. S. Atomic Energy Commission Washington, D. C.

20545

Reference:

Quad-Cities Nuclear Power Station, Unit 1 Docket No. 50-254, License DPR-29, Appendix A Section 1.0. A.2 and 3 2. A.

Dear Mr. Giambusso:

The purpose of this letter is to inform you of the details concerning the setpoint drift of dPIS-1-2353 The setpoint was found to be at 151 inches of water increasing during a routine calibration on February 15 1973 This is contrary to Section 3 2. A. of the Technical Specifications which requires the switch to trip at 5300% (150 inches of water).

The switch is a Barton Model 280.

This switch is used to measure a dP across an elbow tap in the steam line of the HPCI system and will isolate the system on a high flow.

The one inch drift of the switch is considered insignificant with respect to the isolation function.

Drift problems have been encountered previously with this instrument and a setpoint change from 150 inches to 147 Jg inches of water was made in January.

Apparently this is NWA still an inadequate margin to prevent drif t beyond the LCO

${

during the interval between calibrations.

A further decrease in setpoint is being reviewed to increase this margin.

o

$g Very truly yours, Nu

$8 COMMONWEALTH EDISON COMPANY QUAD-CITIES NUCLEAR POWER STATION c( '

E COPY SENT REGION -

g p

c-b'8'N/nwaQ.

M,

    1. /7. - B. B. Stephenson r M' y 1403 Superinte; ~ int BES/zm