Jersey Central Power & Light Company M ADISoN AVENUE AT PUNCH BOWL RO AD e MoRRISToWN. N. J. 07960 e 539-611 I April 7, 1972 b,
8g [A N dpg2
-9 Dr. Peter A. Morris, Director Division of Reactor Licensing United States Atomic Energy Commission
-i JN w}\\. wg 4
l Wshington, D. C. 20545
Dear Dr. Morris:
9s,
Subject:
Oyster Creek Station Docket No. 50-219 Diesel Fire Pump Starting Failure The purpose of this letter is to report to you the failure of Diesel Fire Pump 1-2 to start during a surveillance test on March 21, 1972.
l 1:
m This surveillance test consists of starting each pump from t
the control room and again by lovering the fire pump discharge header
. u, pressure. The pump started on the signal from the control room but
/
did not start on the drop in header pressure. The operator in
(
attendance observed that the diesel cranked very slowly.
Each fire
/'
pump is started by a starting motor driven electrically by a 24-volt DC battery. Each pump is equipped with two, 24-volt DC batteries either of which may be used for starting. Each battery is composed of two heavy-duty 12-volt batteries connected in series. The Shift Foreman on duty went to the fire pump location and by selecting the alternate battery for 1-2 pump, started the diesel although it cranked very slouly, it was determined later that each of the batteries serving the failed pump has one bad cell. The 12-volt batteries which had the baTcell were replaced with new batteries.
In the future, closer attention will be given to possible battery deterioration.
l I Il 7 We are enclosing twenty-five copies of this report.
ANf Very truly yours,
{l).
n.
[f$
hIvan R. Finfr/..f'f(.l#'
v l' i
l(
8304180674 720407 PDR ADOCK 05000219 ock,,Jr.