.o January 21, 1974 Re:

Indian Point Unit No. 2 AEC Docket No. 50-247 Operating License DFR-26 A.O.-4-2-4 Mr. James P. O'Reilly, Director R2gulatory Operations, Region I U. S. Atomic Energy Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 Denr Mr. O'Reilly, hnaccordancewiththerequirementsof.Section6.12.2aofthe Technical Specifications of Facility Operating License No. DPR-26, the following report is submitted.

During the course of a routine plant inspection on January 21, 1974 a small leak was observed at the upstream orifice flange connection for flow transmitter 946D in the six inch residual heat removal sys-tem return line (Line No. 355) to No. 21 reactor coolant loop.

At the time of this observation, the reactor was in the cold shutdown condition with: the residual heat removal system in service and pres-curized to about 400 psig.

The leak is at the base of the fillet weld attaching a 3/4" pipe nipple to the orifice flange and is on the pipe side of the weld.

Preparations for repair of the leak are underway; however, before repairs are initiated, a dye penetrant inspection of the weld will bn made to determine the nature and extent of the defect.

In add-ition our Engineering Department is investigating the occurrence in an effort to detcrmine the cause.

Mr. Anthony Fasano of your office was notified on January 21, 1974 of the circumstances relating to this occurrence.

~

Very truly yours, GNtk.tk b d0d4 1 Warren R.

Cobean, Jr., Manager Nuclear Power Generation

\\