ML20083R133

From kanterella
Jump to navigation Jump to search
Ro:On 720626,during Routine Surveillance Test,Diesel Generator 1 Tripped.Caused by High Engine Temp.Engine Coolant Sys Drained to Permit Removal of Temp Switch
ML20083R133
Person / Time
Site: Oyster Creek
Issue date: 06/30/1972
From: Finfrock I
JERSEY CENTRAL POWER & LIGHT CO.
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20083R132 List:
References
NUDOCS 8303310449
Download: ML20083R133 (2)


Text

-.- -.

3 7

O O

<r n..

\\

a Jersey Central PoweS & Light Company 4

f M ADISON AVENUE A{ PUNCH BOWL RO AD e MORRISTOWN, N.J. 07960 e 539-611I

^

June 30, 1972

.- m I'

\\-

,a i

'J _

V

'+

'//,Y.q s

I Mr. A. Giambusao \\

P Diputy' Dixectderfob Reactor Projects 2

//[f 3/ j f) e Directorate of Licensing

. G-2 [8W

[,Q j! [p

~

Uni *ted, States Atomic Energy Commission Washihgton, D. C. 20545 2.v f.yf "(

y;s m#

g/-

1

Dear:

Mr. Ciambusso:

/

4 4

i

Subject:

Docket 50-219 I

Oyster Creek Station Trip of Diese4 Generator No. 1 j-The purpose of this letter is to report to you a trip of I

diesel generator no. 1 that occurred during surveillance testing at Oyster Creek Station.

On June 26, 1972, a routine one-hour surveillance test of

[.

diesel generator no. I was being conducted when, a normal shutdown 4

sequence of the geierator was initiated. The unit had been loaded at 1875 KW for approximately five minutes prior to the shutdown.

Prior to the shutdown, the unit trouble alarm was annunciated and-the operator, stationed locally at the diesel generator, checked the cause of the trouble alarm and determined Tit to be excescive engine cooling water temperature. The cause.

of the high engine coolant temperature was determined to be 'the prevented the 'shuit'ers (or radiator louvers) 'from ' opening.-resultofadeic[

As a v

result, the engiEe ' water temperature switch (ETS) closed at an

/

approximate coolant temperature of 200 F and initiated a' normal engine' shutdown.

/

The engine coolant system was drained to -permit removal of the TA switch..Upon removal of the. switch, it was found that the gas bulb had lost its charge; thus, s_ replacement switch was./

needed. The manufacturer's representative was contacted. to obtain' a replacement switch and daily surveillance testing of diesel generator no. 2 was started as,re. quired by the Technical Specifications.

A u

!5 [

  • 3 W

!PJdWoEYM f, *'

,,sg.

~oc.~~

.w 7

w' G '

Q, f

+

Q ^ ^7; p.

- 7.

n-e.,

e Mr. A. Giambusso Page 11 l.

June 30, 1972 t

' An investigation is underway to determine what design improvements, if'any, can be made to the louver control system to prevent a recurrence of this event.

l We are enclosiing twenty-five copies of this report.

4 Very truly yours, q

t/

/

Qdhlf) 2)t A.cy J l Ivan R. Finfro,,J j

Manager, Nuclear Generating Stations IRF/pk j

4 Enclosures I

cc Mr. J. P. O'Reilly, Director Regulatory Operations, Region I i

I l

l I

i l

1 t

'ut."

sn:

O

{

1 i

l i

I a

-w y_ - - -

.---54.,-,,.

.- -- s [,

v-,

-