EE BEEEE:

O 4-040052S290 10/17/83 ICS IPPPTZZ CSP PFAB 914739865c PGP TOPT BUCF AN AN :AY 190 10-17 0312P EST O

xd e

'gjtfo d O>

e U.S, NUCLEAR REGULATORY COPHISSION ATTN OR T PURLEY O

REGIONAL ACHINISTRATOR, REGICN 1 631 PARK AVE

""'88**

O e

O e

O CEAR OR reRtEy, e

CN CCIO6ER 17, 1963 hlTH THE PLANT IN A COLD SMUT CCwN CONCITICN, IT O

WAS ESTABLISFEC THAT SCHE OF TFE STEEL PLATES HOLDING THE SEISPIC O

RESTRAINT CCLLARS AT TFE 6 FOOT ELEVATION CF SERVICE WATER PUPPS hup 8ERS.31, 32 AND 36 WERE NOT IN PLACE. A PEELI*IhARY SEISPIC O

AsALYSIS, ASSUSING THE WCRSE CASE CON 0!TICA KITH ALL U PLATES O

REF0VEO, FAS IN0!CATED TFAT PATERIAL'ALLCWANCES WILL BE EXCEECEC AT THE BASE PLATE AND AT THE DISCHARGE THRUST PAD. TPIS EbENT F A L I,5 O

O uNCER THE AURIS 0!CTION OF TECHNICtl SPECIFICATION 6.9.1.7.I, kkICE ADCRESSES STRUCTURES CR COPPCNEtTS REGUIRIhG CORRECTIVE MEASURES TC PREVENT CRERATION IN A MANNER LESS CONSERVATIVE TFAN TFAT ASSUPED IN O

O THE ACCICENT AsALYSIS, A WORK REGUEST FAS EEEN ISSLEC TO CCRRECT TFIS C0h0!TICA PRIOR TO THE PLANT RETURhING TC SERVICE.

O RESIDENT INSPECTCR L RCS$8ACF WAS NOTIFIED AT 1300 HCURS CA OCTCBEE O

17, 1983 THIS TELEGRAF SERVES _AS THE 24 HCUR NOTIFICATION REGUIREC BY TECHNICAL SPECIFICATICN 6.9.1.7 g

g VERY TRULY YCURS O

e

'J O H N C ERONS

' RESIDENT PANAGER O

Is0IAN PCIsr 3 stCLEAR power RLAsi e

O e

PGPCOMP O

e 8312140216 831017 O

PDR ADOCK 05000286 O

S n

PDR R;O e

O TO RERev BY MAILGRAM MESSAGE. SEE REVERSE SIDE FOR WESTERN UNION'S TOLL - FREE RHONE NUMBERS h