GPU Nuclear Corporation i U Muclear
"::st:r **
Forked River, New Jersey 08731-0388 609 971-4000 Wrtter's Direct D al Number:
C321-91-2189 July 23, 1991 U.S. Nuclear Regulatory Commission Attn:
Document Control Desk Washington, DC 20555
Dear Sir:
Subject:
Oyster Creek Nuclear Generating Station Docket No. 50-219 Special Report No. 91-03 Enclosed is Special Report No. 91-03 which is submitted in accordance with technical specificatior. 3.12.E.
This report is overdue because a deviation report was not written when a fire barrier door was declared non-functional. To ensure that reporting requirements are satisfied in the future, this report will be made required reading for all operations department personnel.
If there are any questions, please contact Mr. Michael Heller, OC Licensing Engineer at (609)971-4680.
Sincerely, f &&mJ
}-/
John J. Barton Vice President and Director Oyster Creek JJB\\MH:Jc Enclosure cc:
Administrator, Regica 1 (All w/ enclosure)
Senior NRC Resident Inspector Oyster Creek NRC Project Manager 9107310240 910723 PDR NJOCK 03000219 s
,,i H g(!
GPU Nuclear Corporat.on is a subsid:ary of Genera! Pub!.c Ut.Lt<es Corporatton
/
r Special Report 91-03 Report Date:-
July 2, 1991 Identification of Occurrence:
A non-functional fire barrier door was not repaired within seven days as required by Technical Specification 3.12.E.
Description of Occurrenc_q A review of the fire watch patrol list for the period April 20, 1901 through July 2,1991 identified that the door between fire zones 08-FZ-10A and TB-FZ-118 had been non-functional for greater than seven days.
The door was not able to latch under its own power.
Analysis of Occurrence The subject door is affected by ventilation in the area; it either will not close against air flow or will slam shut causing increased maintenance.
Due to changing area ventilation, the operable status of this door changes frequently.
During the entire period that the dcc was inoperable, an hourly fire watch was established.
The safety significance of this event is minimal.
Corrective Action On July 2,1991, the door was declared operable and the fire watch was secured.
To address the recurring problem with this door, GPUN is evaluating alternate door closing mechanisms.
(C321 91 2189) l
-.