ML20082B965

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Separation Criteria for Power Generation Control Complex Equipment.Initially Reported on 830120.Verification of Electrical Separation Requirements in Test Instructions Now Required
ML20082B965
Person / Time
Site: Nine Mile Point 
Issue date: 10/28/1983
From: Dise D
NIAGARA MOHAWK POWER CORP.
To: Starostecki R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
10CFR-050.55E, 10CFR-50.55E, 7611, NUDOCS 8311210385
Download: ML20082B965 (2)


Text

t

~

NUMOHAWK Y NIAGARA NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST, SYRACUSE. N.Y.13202/ TELEPHONE (315) 474-1511

)

October 28, 1983 (7611) l Mr. R. W. Starostecki, Director U.S. Nuclear Regulatory Commission Region I Division of Project and Resident Programs 631 Park Avenue Kit.; of Prussia, PA 19406 Re: Nine Mile Point Unit 2 Docket No. 50-410

Dear Mr. Starostecki:

Enclosed is a final report in accordance with 10CFR50.55(e) for the problem concerning separation criteria for Power Generation Control Complex (PGCC) equipment. This condition was reported via telephone to Mr. J.-Wiggins of your staff on. auary 20, 1983 and was followed by interim ~ reports dated February 23, 1983 and August 9, 1983.

Very truly yours, D. P. Dise Vice President quality Assurance DPD/TL:ja

. Enclosure xc: Director of Inspection and Enforcement' U.S. Nuclear Regulatory Commission Washington, DC 20555 Mr. R. Gramm, Resident Inspector 0-l,

8311210385 831028

/v PDR ADOCK 05000

/

'g g s

e.6*

Final Report for a Problem L

Concerning Separation Criteria for the Power Generation Control

}

Complex _ (PGCC) Equipment i-t-

Description of the Deficiency i

A review by-Niagara Mohawk Quality Assurance identified that required notes concerning separation criteria, which appear on the system elementary diagrams, were-not included on.the. corresponding-connection diagrams or implemented in the connection diagrams wiring.

Therefore, these requirements.

werejnot incorporated into the PGCC hardware.

The electrical separation t

criteria notes concern the wiring of'certain power monitor and test relays.-

r

~

Analysis of Safety Implications i

l This deficiency resulted from a General Electric Quality Control and Engineering failure-to identiff all separation _ criteria deficiencies prior.to shipment to the Nine Mile Point Unit 2 site.

There.is a possibility that if this problem.were to have remained' uncorrected, it could have adversely affected the. safe-' operation of the plant.. 'A detailed analysis _of Safety Implications was not performed.

Corrective Action General-Electric has added separation. notes'to several connection diagrams asL a result of this deficiency. Subsequent to this action, Niagara Mohawk j

Quality Assurance performed a review of all' safety related connection-diagrams requiring electrical separation and found the required separation notes.

i General Electric has corrected all the monitoring and tes't relay; wiring located at the General Electric' shop except for one relay.

The remaining

  • relay will-be corrected at the Nine Mile l Point Unit 2 site by_ June 30, 1984;.

i As.a result of Niagara Mohawk's Quality. Assurance informing ' General Electric :

of' the electrical separation deficiencies in the as-shipped (PGCC modules, a.

paneliby panel : inspection lwas' performed at'the'~ site of all safety 'relatedi

.L

. panels for which electrical-separation is required. ; General-Electric Field.

Deviation-Disposition Requests-(FDDR's)-and Field.DispositionLInstructions;

.(FDI's):will be written to correct the separation deficiencies'..cThis rework.

l.

will:be completed by_. June.30 1984..

l-In order to prevent -recurrence of this: condition,4the followinglactions have ;

been taken in' General Electric's. manufacturing shop:

l 1'

.1. :The verification ~ofielectrica!~ separation-requirements in: Test.

InstructionsL(TI's)lisjow re' uired ' asia -backup to theLnorma1Einspection :

q 4

of. panels toTassure thatill' separation requirements.are met.;

~

~

L

^

2. - Round -table discussions
(mini-training classes) have:oeen: held with.

I f Quality Control personnel)(inspectors tand!. testers) for the"purposefof __ -

i,I describing;the changessin~the Test-Instructions 5as-welllas reviewing the 4

separationiinformation-wh'idh appears 7a's; notes lon theLdrawings.

^

j

' ~o n

m.

s

. o q

'l y,

y

.I L -'

,f x,

+

-