Text
.
I J
Attcchment IV to CO 95-0003 Page 1 of 2 l
l I
t ATTACHMENT IV PROPOSED TECHNICAL SPECIFICATION CHANGES P
t
)
9503270304 950321 PDR ADOCK 05000482 p
.. ~ -
f Attachment IV to CO 95-0003 Page 2,cf 2 t
(
i i,
CONIAINMENT SYSTEMS i
I 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS I
CONTAINMENT SPRAY SYSTE,M i
LIMITING CONDITION FOR OPERATION t
i 3.6.2.1 Two independent Containment Spray Systems shall be OPERABLE with each Containment Spray System capable of taking suction from the RWST and transfer-ring suction to the containment sump.
l APPLICABILITY: MODES 1,2,3, and 4.
t ACIl0N:
t With one Containment Spray System inoperable, restore the inoperable Contain-ment Spray System to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT
[
STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; restore the inoperable Containment Spray Sys-
~
tem to OPERABLE status within the next 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in COLD SHUTDOWN within I
the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
(
I SURVEILLANCE tlEQUIREMENTS
[
4 6.2.1 Each Containment Spray System shall be demonstrated OPERABLE:
- a. At least once per 31 days by verifying that each valve (manual,
[
power-operated, or automatic) in the flow path that is not locked, y
sealed, or otherwise secured in position, is in its correct position;
- b. By verifying, that on recirculation flow, each pump develops a discharge pressure of greater than or equal to 250 psig when j
tested pursuant to Specification 4.0.5;
- c. At least once per 18 months during shutdown, by:
- 1) Verifying that each automatic valve in the flow path actuates to its correct position on a Containment Pressure-High-3 (CSAS) test signal, and
- 2) Verifying that each spray pump starts automatically on a Containment Pre ure-High-3 (CSAS) test signal.
l i
- d. At least once per.E^ years by performing an air or smoke flow test l
through each spray header and venfying each spray nozzle is unobstructed.
i L
WOLF CREEK - UNIT 1 3/4 6-13 L