Text

..

i 4

.s i

ATTACHMENT 2 TO LAP-83-450 PROGRAM OUTLINE A Measure of the Voltage Withstand Level on Raychem Cable Samples After Exposure to Simulated LOCA 1

l f

f 4

1 I

f i

1 I

i i

c B310260148 831020 PDR ADDCK 05000324 P

PDR 4

=

r.

CAROLINA POWER & LIGHT COMPANY A MEASURE OF THE VOLTAGE WITHSTAND LEVEL ON RAYCHEM CABLE SAMPLES AFTER EXPOSURE TO A SIMULATED LOCA FOR CAROLINA POWER & LIGHT COMPANY BRUNSWICK STEAM ELECTRIC PLANT - UNITS 1 & 2 i

l l

l l

REV.NO.

RECOMMENDED BY CONCURRED BY APPROVED BY DATE

, AWN, s/2d, er dal x se i

r 8

l

[

m

..m.-.

m m

o.

1.

OBJECTIVE To determine the extent to which the cables may exhibit residual margin upon completion of the aging and harsh environment exposure described in Reference 7.1.

2.

SCOPE-The testing described herein will be performed on cable specimens used in the program described in Reference 7.1.

That program is intended to 1

demonstrate qualification of the cable for use in Class IE service in primary and secondary containment at BSEP. Similarly, the post-LOCA test-ing described below is intended to determine residual margin in addition to those margins of time, temperature, pressure, voltage and current accounted for in Reference 7.1.

Because neither of these programs is concerned with generic qualification of the cable, there is no residual margin requirement once the cable specimens have met the performance re-quirements specific to BSEP, as described in Reference 7.1.

3.

CABLE DESCRIPTION The cable to be subjected to the high voltage withstand test described below will be the identical specimens used in LOCA tests described in Reference 7.1.

4.

PROCEDURE 4.1 At the conclusion of the LOCA testing, the cable ends will be cut inside the pressure vessel and the mandrels, with the cables still attached, will be removed from the vessel.

4.2 The cables will then be removed from the mandrels without uncoiling.

4.3 The ends of each specimen will be prepared by removing a short length of the jacket and stripping the primary insulation from each conductor to facilitate electr,1 cal connections.

4.4 The center portion of each cable will be immersed in tap water at room temperature.

4.5 With the water bath grounded, the conductors will be connected as 1

shown in Figure 1, Configuration A.

J 4.6 _A withstand voltage of 1200 volts will be applied by uniformly increasing the applied voltage from zero to maximum at a rate not exceeding 500 volts /second, holding 1200 volts for 5 minutes and decreasing the voltage to zero in not less than 3 seconds.

(1) 4

--,-7--

,y.,

t-y--

.y,-

_-m, c,.,

1.-

y

~

~

~

s 4.7 The connections will then be changed to confot= with Figure 1, Configuration B, and a second voltage withstand test performed in accordance with 4.6 above, except that at the end of the 5 minutes period, the voltage will be increased at a uniform rate, not exceeding 500 volts /second, to a value of 3600 volts, held for 5 minutes and then reduced to zero in not less than 5 seconds.

4.8 The connection will then be changed to conform to Figure 1, Configuration A.

A withstand voltage of 3600 volts will then be applied by increasing the applied voltage from zero to maximum at a rate not exceeding 500 volts /second, holding for 5 minutes and then decreasing the voltage to zero in not less than 5 seconds.

5.

MEASUREMENTS The voltage applied to the test specimens will be measured and recorded.

6.

DOCUMENTATION An information report will be furnished by the testing facility.

7.

REFERENCES s

7.1

" Demonstration of Raychem Cable for Qualified Use in Class 1E Service at BSEP - Primary & Secondary Containment," Revision 2.

(2)

~

[

/

/

N

\\

7 2

fo 1

3'i g

/

S 4

/

s

/

Figure 1.

Connections for Voltage Withstand Test Configuration A:

1, 3, 5 and 7 connected to high voltage terminal.

2, 4 and 6 grounded.

Configuration B:

1, 3, 5 and 7 grounded.

2, 4 and 6 connected to high voltage terminal.