ML20080T335

From kanterella
Jump to navigation Jump to search
Forwards Sc Dept of Health & Environ Control & Util 830912 Response to Noncompliances Noted During 830711-13 Insp of NPDES Permit SC0030856.Corrective Action Will Be Completed by 831015
ML20080T335
Person / Time
Site: Summer 
Issue date: 10/18/1983
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
References
NUDOCS 8310200252
Download: ML20080T335 (5)


Text

.

'e

  • e.

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFIC,764 cOWMBIA. SOUTH CAROUNA 29218

o. w. oixe :. ;n.

nue,'["o,.'"*o October 18, 1983 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.

20555

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 NPDES Non-Compliance

Dear Mr. Denton:

South Carolina Electric and Gas Company (SCE&G), in compliance with Appendix B of the Operating License for the Tirgil C.

Summer Nuclear Station, hereby submits a copy of the correspondence between the South Carolina Department of H6alth and Environmental Control (DHEC) and SCE&G concerning NPDES Permit No. SC0030856 non-compliances.

The Staff was inadvertently omitted on distribution of this information at the time SCE&G originally submitted our response to DHEC.

Should you have any questions, please advise.

Ver truly yours, 64 O. W.

Di on WRM:OWD/fjc cc:

V. C.

Summer C.

A.

Price T.

C. Nichols, Jr./O. W. Dixon, Jr.

A.

R. Koon E.

H.

Crews, Jr.

C.

L. Ligon (NSRC)

E.

C. Roberts G. J.

Braddick D.

J. Richards H. N.

Cyrus J.

P. O'Reilly NRC Resident Inspector J.

B.

Knotts, Jr.

Group Managers O. S. Bradham NPCF N.

E.

Clark File (Lic./Eng.)

I

\\

8310200252 831018 PDR ADOCK 05000395 G

PDR l I

BOARD J. trwin Mrson, Jr., M.D., Chiirman Gerald A. Kaynard, Vice-Chairman C

Leonard W. Douglas, M. D., Secretary LdM.LtD FAIL Oren L. Brady, Jr.

REIURN R Wr REQU NP Moses H. Clarkson, Jr.

_._A 9

Barbara P. Nuessie V

I James A. Sprulil, Jr.

{

]

August 30, 1983 COMMISSIONER Robert S. Jackson, M.D.

2600 Bull Street Columbia, S.C. 29201 Mr. R.B. Clary Manager of Nuclear Licensing ~

SCE&G RE:

SCE&G/Sumer Nuclear I P.O. Bcoc 764 Columbia, S.C.

29218 NPDES Permit #SC0030856

.Fa, r-Fw,ld County

Dear Mr. Clary:

Attached, please find NPDES Cmpliance Inspection Report and Cmn1iance )bnitoring Report which contain the results of DHEC staff's July 11-13, 1983 inspection of your waste treatment facility. During this sampling period, the sample chain of custody was Inalntained by DHEC personnel and samples were split with your operator. Sampling was perforned as specified in your NPDES permit.

A review of this data reveals that the wastewater discharge frcm the referenced facility was meeting applicable NPDES pemit effluent limitations during the M14ng period.

However, based upon the unsatisfactory ratings noted cn the 3560-3 report, this facility has been given a non-compliance rating for this partimlar inspection.

Since this facility has received a non-ccmpliance rating, you are regaested to rescand within thirty (30) days concerning corrective action. A copy of ycur respcose should also be subnitted to the DHEC Envircmental Oaality Ctatrol Office at the follow-ing aMress:

Mr. Joe Rucker, Director ECC Office Pearl leitzey Buildir#3 State Park, S.C.

29147 Failure to respond or an inadequate response will provide a basis for further enforement action, if ccmsidered necessary.

Sincerely, Marvin P. Murray Environmental Quality Manager j

gpy g Enforcement Section Water OJality Assessment and Attachment Enforcement Division cc: District Director Doug Lankford Steve Th mas Enfcrce ent Secticn

{

l

..C. Electric & Gas Company

C;Su=merjuelearStation NPDES No. SC0030856
..
. lon A NPDES parmit has expired but company will continue to operate under expired permit until new one is issued.

tecticn G - a (i)

No sampling time'on lab sheet.

(ii)

No time for beginning of analysis and completion.

(iv)

Analytical method used not posted on lab sheets.

e-No quality assurance records.

'tetion H (a)

Permit has expired.

Company is to operate under old one until new one is issued.

(1) 006 is two discharge recorded as 006A and 006B.

Snction I (g<)1 Oil is skimmed and is taken by waste oil company - outfall 006B. f 2:

Se,ction K-P' art 1 Outfall 001 - pump log.

004 - orfice in line.

005 - 900 V-notch weir.

006-A&B 90 V-notch weir.

007 - batch dump 008 - 900 V-notch weir All V-notch weirs do not have proper design.

Some are too thick and no knife edges. Dis-cusstd with Mr. Johns the proper design.

Part 2 - c - 1 Samples-are not iced during collection of composite on 005.

Discussed with Mr. Johns.

Part 3 - a ASTM prpcedures used.

d DO meter calibration is by temperature and air.

Is never checked by Winkler method.

Quality control procedures have not been completed.,

e Lab cupervisor'has requested meeting with Lab Certification Section of this agency for guid-ence in bringing lab up to requirements.

Saction L Outfall 003 - All radiological sampling is performed by the Radiological Division of this agency.

Only one discharge for~006 is permitted.

This discharge has been changed to two discharges -

006A and 006B.

i

~*

SOUTH CAROLINA ELECTRIC & GAS COMPANY POS7 CPFICE 704 CotuuntA. south CAROLINA 29218 C. W. DixoN. JR.

vics Passioeur September 12, 1983 avetain o,...r, I

Mr. Marvin P.

Murray W-

,Environmantal Quality Manager Enforcement Section South Carolina Department of Health and Environmental Controls 2600 Bull Street Columbia, South Carolina 29201

SUBJECT:

SCE&G/ Summer Nuclear I NPDES Permit #SC0030856 Fairfield County

Dear Mr. Murray:

The following information is submitted in response to your letter dated August 30, 1983, in which you notified this f acility of a non-compliance rating for our waste treatment unit.

Individual responses are listed by item number as found in the NPDES Compliance Inspection Report (EPA Form 3560-3) :

Lab sheets are being revised to include Sect. G (a)(i) sample time.

(a)(ii)

- Lab sheets are being revised to include analyses start and stop times.

Lab sheets are being revised to include (a) ( iv)

Analytical Proce'dures used.

(e)

- All NPDES records are maintained for a minimum of five years.

Quality Control sample results will be maintained in the same manner.

As indicated, our permit has expired.

Sect. H (i)

It is being re-written and will include discharge points 006A a.nd 00 6B.

Sect. I (k)

- Chemistry Procedure CHP-604, " Water Treatment Plant and NPDES Monitoring," is being revised to include operation and maintenance inrtructions for the waste treatment facilities.

\\

Mr.

Marvin P.

Murray NPDES Permit #SC0030856 Fage Two September 12, 1983 Sect. K, Part 1(a)

- All improperly designed Weirs have been replaced with properly designed units.

Sect. K, Part 2(c)(i) - A 48-quart ice chest has been ordered to properly refrigerate samples during compositing.

Sect.

K, Part 3(d)

- Calibration of Dissolved Oxygen Meter is being revised to include a monthly check by the Winkler Method.

Sect.'K, Part 3(e),

- Quality Control Procedure to be issued Sect.

K, Part 3(f), &

containing requirements for NPDES Sect. K, Part 3(g)

QC Program, including performance of 10%

Duplicate Samples on TSS, Iron, Copper, BOD, and Fecal Coliform; and 10% Spike on Iron and Copper.

These requirements are per " State of South Carolina Department of Health and Environmental Control Environmental Laboratory Certification Criteria."

It is intended that all changes, as stated above,. will be completed by October 15, 1983.

If you have any questions regarding this matter, please contact Frank Bacon at (803) 345-5209, Ext. 4156.

Very truly yours, i

O. W.

Di on r.

ARK:OWD/mac/fjc cc:

W.

F. Bacon A.

R. Koon S.

E.

Summer R._B.

Clary i

File Mr. Joe Rucker EQC Office Paul Leitzey Building State Park, S. C.

29147

/