NIAGARA MOHAWK POW IR CORPORATION NIAGARA MOHAWK 300 ERIE SOULEVARD WEST synaCUSE,N Y 13202 GERALD K. RHODE SENIOR VICE PRESIDENT February 1,1984 (8016)

Mr. R. W. Starost,ecki, Director U.S. Nuclear Regclatory Conunission Region I Division of Project and desident Programs 631 Park Avenue King _of Prussia, PA 19406 Re: Nine Mile Point Unit 2 Docket No. 50-410

Dear Mr. Starostecki:

Enclosed is an interim report in accordance with 10CFR50.55(e) for the problem concerning actuators furnished by G. H. Bettis (55(e)-84-02).

This problem was reported via telecon to Mr. S. Collins of your staff on January 4, 1984.

Very truly yours,

/

2s uQ^> / %W G.' K. Rhode Senior Vice President GKR/TL:ja Enclosure xc: Director of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 Mr. R. Gramm, Resic'ent Inspector 8402240000 840201 PDR ADOCK 05000410 S

PDR

+

fi4t

s NI AGARA MOHAWK POWER CORPORATION NINE MILE P0 INT UNIT 2 DOCKET N0. 50-410 Interim Report for a Problem Concerning Actuators Furnished by G. H. Bettis Description of the Problem The Pacific Air Products Co. is supplying safety-related dampers in HVAC '

systems for Nine Mile Point Unit 2.

The G. H. Bettis Company has notified Pacific Air Products Co. of a problem with actuators suppliea to Pacific Air Products Co. These actuators are safety related, Quality Assurance Category I and are used in the reactor building roof ventilation system dampers for Nine Mile Point Unit 2.

Based on information provided by G. H. Bettis, the degradation of seals, due to a chemical reaction between the elastomer and lubricant, may prevent the actuator from operating the damper.

This problem was reported to the NRC by G. H. Bettis Company under 100FR21 on November 18, 1983.

This matter is under investigation and a final report will be submitted by March 16, 1984.