Notifies of Occurrences Re Transamerica Delaval Diesel Generators.Minor Amount of Cylinder Head Leakage & Slight Crack Noted.Flaws in Welds Joining Ball to Pipe of Generator 1-A Pushrods Discovered.No Matters Significant
ML20080N527
Person / Time
Site: Catawba  
Issue date: 02/17/1984
From: Mcgarry J
BISHOP, COOK, PURCELL & REYNOLDS, DUKE POWER CO.
To: Foster R, Kelley J, Purdom P
Atomic Safety and Licensing Board Panel
References
NUDOCS 8402220275
Download: ML20080N527 (2)


Text

,

00f.. -

US?h.

LAW Orncc5 o'

'84 EB 21 02...

BISHOP, LIBERM AN, COOK, PURCELL & REYNOLDS in NEw wpe K B2OO SEVENTEENTH STR E ET, N. W.

^

WAS HIN GTON, D. C. 2 00 36 gig wQp, LIB E A

&CQQM 26 emoAowAv (2C 2) 857-9800 NtwyoRK N tw YORM 10Q04 (212)248-69 00 TELEX 440$74 INTLAW Ut TELtx 222767 February 17, 1984 Mr. James L. Kelley Chairman Atomic Safety and Licensing Board Panel U.S. Nuclear Regulatory Dr. Paul W.

Purdom Commission 235 Columbia Drive Washington, D.C.

20555 Decatur, Georgia 30030 Dr. Richard F. Foster P.O. Box 4263 Sunriver, Oregon 97702 Re:

Duke Power Company, et al. (Catawba Nuclear Station, Units 1 and 2),

Docket Nos. 50-413, 50-414 Gentlemen:

The Board now has pending before it a decision with respcct to Palmetto Alliance's motion for a new contention with respect to the Transamerica Delaval diesel generators at Catawba.

In light of that, we believe we should bring to the Board's attention that, in the course of long-term durability tests being conducted with the 1-A diesel gener-ator at Catawba, certain matters have occurred with respect to one cylinder head, one or more valve pushrods, one of the two turbochargers on the engine, and a fuel oil injection pump nozzle.

More specifically, a minor amount of cylinder head leak -

age was noted during a run; when the engine was shut down it was discovered, during the week of February 5, that there was a slight crack in that cylinder head.

Also during that week, the pushrods for diesel generator 1-A were checked, and it was determined that some had flaws in the welds joining the ball to the pipe.

We would note that all the pushrods on diesel generator 1-A were subsequently replaced with pushrods i

8402220275 340217 DR ADOCK 05000 p0D

'9.

of an improved design.

During the same week, one of the turbochargers showed excessive ware on the rear bearing due to inadequate lubrication, a lube oil drain line leak, and a rupture of the lube oil prelude line for that turbo-charger.

Finally, during this run, a fuel oil injection pump nozzle was found to be cracked.

It should be noted that, with the exception of the fuel oil injection pump nozzle, these matters are similar in nature to matters found with other TDI diesels, as reflected in the February 2, 1984 " Report of Meeting with Representatives of the Transamerica Delaval, Inc. (TDI) Emergency Diesel Gener-ator Owner's Group" which was served on the parties to this proceeding.

It is Applicants' view, however, that none of these matters have a significant bearing on the operational reliability of the diesel.

Respectfully submitted, 1]p J.

Michael McGarry, II cc:

All Parties (Hand delivered to Kelley and Guild) l L._