INSTRtMENTATION.

SOURCE RANGE MDNITORS-i LIMITING CONDITION FOR OPERATION 3.3.7.6. At least three source range monitor channels shall be OPERABLE.

APPLICABILITY: OPERATIONAL CONDITIONS 2*, 3 and 4.

ACTION:

l In OPERATIONAL CONDITION 2* with one of the above required source a.'

range monitor channels inoperable, restore at least 3 source range monitor channels to OPERA 8LE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at least HDT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

b.

In OPERATIONAL CONDITION.3 or 4 with two or more of the above required source range monitor channels inoperable, verify all insertable con-trol rods to be fully inserted in the core and lock the reactor mode l

switch.in the Shutdown position within one hour.

SURVEILLANCE REQUIREMENTS 4.3.7.6 Each of the above required sourcie range monitor channels shall be demonstrated OPERABLE by:

l a.

Performance of a:

1.

CHANNEL CHECK at least once per:

4 a) 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> in CONDIT;3N 2*, and b) 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in CONDITION 3 or 4.

2.

CHANNEL CALIBRATION ** at least once per 18 months.

b.

Performance of a CHANNEL FUNCTIONAL TEST:

1.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> prior to moving the reactor mode switch from the Shutdown position, if not performed within the previous 7 days, and 2.

At least once per 31 days.

Verifying, prior to withdrawal of control rods, that the SRM count c.

rate is at least f cys with the detector fully inserted.

o.7 l

Nith IRM's on range 2 or below.

    • Neutron detectors may be excluded from CHANNEL CALIBRATION.

GRAND GULF-UNIT 1 3/4 3-73 8309140039 830912 PDR ADOCK 05000416 P.

PDR

TA8tE 3.3.6-2 s

j CONTROL 1100 BLOCK INSTRLMENTATION SETPOINTS

~

5 TRIP FUNCTION' TRIP SETPOINT ALLOWA8LE VALUE

. o i

1.

ROO PATTERN CONTROL SYSTEM E

a.

Low Power Setpoint 20 + 15. -UX of RATED THERMAL 20 + 15, -05 of RATED THERMAL POWER i

Q POWER i

b.

Intermediate Rod Withdrawal

< 70% of RATED THERMA! POWER

< 70% of RATED THEllMAL POWER y

j Limiter Setpoint 2.

APRM i

a.

Flow Blased Neutron Flux-Upscale

< 0.66 W + 42%*

< 0.66 W + 45%*

i b.

Inoperative NA NA c.

Downscale

> 5% of IIATED THERMAL POWER

> 3% of RATED THERMAL POWER

~

~

l d.

Neutron Flux - Upscale Startup i 12% of RATED THERMAL POWER 1 14% of RATED THERMAL POWER i

3.

SOURCE RANCE MONITORS l

i l

Y a.

Detector not full in MA NA g

b.

Upscale

< 1 x 10 cps

< 1.5 x 10$ cps 5

i c.

Inoperative NA NA 3

j d.

Downscale 1-t cps 1 e-cps 0.7 o.5 4.

INTERMEDIATE RANGE MONITORS 5

a.

Detector not full in MA NA j

b.

Upscale

< 108/125 of fu41 scale

< 110/125 of full scale c.

Inoperative NA NA 1

d.

Downscale 1 5/125 of full scale 1 3/125 of full scale

]

5.

SCRAM DISCHARGE VOLUME

_ 33.5 inches

_ 32 inches a.

Water Level-High g

6.

REACTOR COOLANT SYSTEM RECIRCULATION FLOW

)

a.

Upscale i 108% of rated flow 1 111% of rated flow h

I D

l 1

l "The Average Power Range Monitor rod block function is varied as a function of recirculation loop flow n

[

]

(W).

The trip setting of this function must be maintained in accordance with Specification 3.2.2.

_