Supplemental Final Deficiency Rept Re Potential Deterioration of Isoprene Gaskets on Standby Diesel Generators.Initially Reported on 821217.Corrective Action Completed by 831228.Also Reported Per Part 21
ML20079P158
Person / Time
Site: Bellefonte  
Issue date: 02/28/1983
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21-83 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8303040542
Download: ML20079P158 (1)


Text

TENNESSEE VALLEY AUTHORITY CH ATTANOOGA. TENNESSEE 374ol 400 Chestnut Street Tower II February 28, 1983 BLRD-50-438/83-08 BLRD-50-439/83-05 j'

'{

v 'c' v

'$. -p

$p 3 o

U.S. Nuclear Regulatory Commission Region II M

-d Attn:

Mr. James P. O'Reilly, Regional Administrator i:)k 101 Marietta Street, Suite 3100 9

93 Atlanta, Georgia 30303 3

'(..

f v

Dear Mr. O'Reilly:

y-BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - POTENTIAL DETERIORATION OF ISOPRENE GASKETS ON STANDBY DIESEL GENERATORS - BLRD-50-438/83-08, BLRD-50-439/83 SUPPLEMENTAL REPORT The subject deficiency was initially reported to NRC-0IE Inspector Linda Watson on December 17, 1982 in accordance with 10 CFR 50.55(e) as NCR BLN MEB 8209. This was followed by our final report dated January 24, 1983 As discussed with NRC-0IE Inspector Linda Watson on February 17, 1983, the date of February 18, 1983, for completion of corrective actions indicated in our final report on this matter would not be met. Installation of the new gasket is not reconnended until immediately before operation of the generator. Thic information was provided by the vendor, TransAmerica Delaval, Inc., of Oakland, California. Initial test operation of the generator has been rescheduled for December 28, 1983 Therefore, the corrective action on this matter will be completed by December 28, 1983 We consider 10 CFR Part 21 to be applicable to this deficiency.

If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, nager Nuclear Licensing oc:

Mr. Richard C. DeYoung, Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission p

Washington, D.C.

20555 owicIAL '

D

.bA 8303040542 830228 M

DR ADOCK 0500043g

'l__ /-/p/

PDR hf An Equal Opportunity Employer

.