Text

'

REVISED PAGE -- JANUARY 13, 1984 Director, Office of Resource Management S3ptember Monthly Operating Report Page 4 October 14, 1983 ATTACHMENT III UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50/395 UNIT V.

C.

SUMMER I DATE 10/14/83 COMPLETED BY G.

J.

Taylor TELEPHONE (803) 345-52C9 (1)

METHOD OF (2)

TYPE SHUTTING DOWN F: FORCED DURATION THE REACTOR OR CORRECTIVE ACTIONS /

NO.

DATE S: SCHEDULED (HOURS)

REASON REDUCING POWER COMMENTS 14 830906 F

14.3 G

3

14) Reactor Trip on low-l low Steam Generator level due to steam line p" essure transmitter calibration, procedure error.

15 830911 F

10.6 A

3

15) Reactor Trip, l

caused by loss of offsite power source.

16 830917 S

10.1 B

1

16) Turbine off line for ]

maintenance of permanent magnet generator power supply.

17 830928 F

0 A

4

17) Turbine Runback due l

to Hi Stator Water Cooling System temperature.

Reactor power reduced by rod insertion and emergency boration.

I 8401270389 840113 DR ADOCK 050003g