ML20079K258

From kanterella
Jump to navigation Jump to search
Proposed Tech Spec Table 3.8-1, Containment Penetration Conductor Overcurrent Protective Device Test Setpoint Criteria
ML20079K258
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 01/18/1984
From:
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
Shared Package
ML20079K240 List:
References
NUDOCS 8401240563
Download: ML20079K258 (1)


Text

.

/

ss

  • e BW t

i Ra

'5 Om Attachment I 88 TABLE 3.8-1 (continued) 8 4 *ll CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICE 18 POINT CRITERIA

_ EQUIP. NO. SYS/ DESCRIPTION DEVICE LOCATION TEST SETPOINT XVG 8811A - Recirculating RESPONSE TIME 171)

Sump to RHR Pump Prima ry XMClDA2Y/9IM 150 AMPS f 200 sec.

"A" - Isolation Valve Backup XMClDA2Y/9IM 150 AMPS 5 200 sec. 172) XVG 8811B - Recirculating Sump to RHR Pump Primary XMClDB2Y/22CG 150 AMPS f 200 sec.

"B" - Isolation Valve Backup XMClDB2Y/22CG 150 AMPS f 200 sec. 173) XVG 3004A-RB Sump Isolation Valve Prima ry XMCIDA2Y/17IM 225 AMPS N/A Backuo XMClDA2Y/17IM 45 AMPS

$ 100 sec. 174) XVG 3004 B-RB Sump Isolation Primary XMClDB2Y/2IM 225 AMPS N/A Valve Backup XMClDB2Y/2IM l

45 AMPS I

$ 100 sec.