ML20079G049

From kanterella
Jump to navigation Jump to search
Proposed Tech Spec 3.12/4.12, Fire Protection Sys
ML20079G049
Person / Time
Site: Quad Cities  
Issue date: 09/30/1991
From:
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20079G045 List:
References
NUDOCS 9110080385
Download: ML20079G049 (20)


Text

_- - _ _

t i

QUAD-CITIES DPR-29 3.12/4.12 f!RE PROTECTION SYSTEMS

}

LIMITING CONDITIONS FOR OPERATIONS SURVE]LLANCE REQUIREMINTS Applicability:

Applicability:

Applies to the fire protection systems Applies to the periodic testing require-whenever the equipment or systems being ments of the fire protection systems protected are required to be operable.

whenever the fire protection systems are required to be operable.

i Objective:

Objective:-

To ensure that adequate protection To verify operability of the fire protec-against fires is maintained during all tion systems.

modes of facility operation.

- i SPECIFICATIONS A.~- Fire Detection Instumentation A.

fire Detection Instrumentation 1

1.

As a minimum the fire detection 1.

Each of the fire detection instrumentatIonforeachfire instruments given by lable detsction zone shown in Tuble 3.12-1 shall be demonstrated 3.12-1 shall be operable at all operable at least once per 6 times when equipment in that months by a channei-functional fire detection zone ir required

test, to be operable.

i 2.

With the number of operable fire 2.

All non-supervised circuits detection instruments less than shall be demonstrated operable required by Table 3.12-1:

once per month.

a.

Perform an inspection of affected. zone, within I hour.

Perform additional inspections at~least once per hour except in inacces-sible areas, b.

Restore the inoperable instrument (s) to opereble status within 14 days or prepare and submit a report to the Commission pursuant l-L 3.12/4.12-1 Amendment No. 114 9110080335 910930 ADOCtt 0500cr254 PDR PDR P

g w e-

+ e s e t s w--

e yr

<+4,---,,

en

-e-.ee,,-

w--#,g.m,w,rs,.+-4-.,w ww W w.ww E s d.-

c ~ 3 4 % --%w w., e., w<= wc -.w,syw s-r w w w we e

,,.. wir*,.m y-ureewc

f i

r QUAD Clill5 DPR 29 r

to Specification 6.3.A.1 within the next 30 days outlinin cause of the malfunction,g the the action taken, and the plans for restoring the instrument (s) to operable status.

-3.

The provisions of Specification 3.0.A are not applicable.

B.

Fire Suppression Water $ystem B.

Fire-Suppression Water System 1.

The Fire suppression Water Sys-1.

The fire Suppression Water tem shall be operable at all tystem shall be demonstrated times with:

operable:

u a.

Two (2) high pressure pumps a.

At least once per 31 days on each with a capacity.of 2000 a-staggered test basis by ppm with their discharge starting each pump and

-i aligned to.the fire operating it for at least 20 suppression header, minutes on recirculation flow.

~ b.- Automatic initiation logic b.

At least once per 31 days by for each fire pump.

verifying that each valve (manual, power operated or automatic) in the flow path is in the correct position.

c.

An operable flow path cap-c.

At least _once per year by able of taking suction from performance of a system the Mississippi River and flush.

transferring the water l

through distribution piping u

with operable sectional-.

L izing control or isolation valves to the yard hydrant 1-curb valves and the front valve ahead of the water flow alarm device on each sprinkler, hose stand pipe, or spray. system riser.

g 3.12/4.12-2 Amendment No. 114

__-.. _ _.._~ _...._ -..._._. _..--. _,_ _

QUAD-ClllES i

DPR 29 i

d.

At least once per year by cycling each testable valve in the flow path through at least one complete cycle of full travel, e.

At least once per operating cycle

1) By performing a system functional test which includes simulated automatic actuation of the system throughout its operating sequence and verifying that each automatic valve in the flow path actuates to its correct position.
2) By verifying that each pump develops at least 2000 gpm at a system head of 123 psig.
3) Cycling each valve in the flow path that is not testable during plant operation through at least one complete cycle of full travel, and f.

At least once per 3 years by performing flow tests of the system in accordance with Chapter 5, Section 11, NFPA fire Protection Handbook.

3.12/4.12-3 Amendment No. 114

QUAD-C111tS DPR-29 2.-

With inoperable fire pumps or associated water supply, restore the inoperable equipment to operable status within 7 days, or prepare and submit a report to the Commission pursuant to Specification 6.3.A.1 within the next 30 days outlining the plans and procedures to be used to I

provide for the loss of redun-dancy in this system.

3..-

With no fire Suppression Water System operable, within 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

a.

Establish a backup fire Suppression Water System, b.

Notify the. Commission i

pursuant to Specification 6.3.A.1 outlining the actions taken, tlie cause of the inoperability, and the plans and schedule for j

restoring the system to operable status.

4 If the requirements of Specifi-cation 3.12.B.3.a cannot be met.

an orderly shut down shall be

-initiated, and'the reactor shall be in a' cold shut down condition within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

C.

Sprinkler Systems C.

Sprinkler Systems 1.

The sprinkler systems given in 1.

At least once per year by cycl-Table 3.12-2 shall be operable ing each testable valve in the at all times when equipment in flow path through at least one.

the areas spray / sprinkler pro-complete cycle of full' travel..

tected is required to be oper-able.

3.12/4.12-4 Amendment No. 114

.,.cwE<rw

~e-.w-

- w. + -

- + - - - - - * * * - * * '

""N"'

' - * ' ' '"^

~

1 4

'l QUAD CIll[S DPR-29 2.

With a sprinkler system inoper-2.

At least once per operating able, establish backup fire sup-cycle:

i pre *.sion equipment and inspect the area twice per shift.

a, A system functional test shall be performed which includes simulated auto-matic actuation of the sys-

- tem and verifying that the automatic valves in the flow l

path actuate to their correct positions.

b.

The sprinkler headers shall

- be inspected to verify their-integrity.

c.

Each nozzle shall be-inspected to verify no blockage.

3.

Restore the system to operable 3.

At least once per 3 years by status within 14 days, or performing an air flow test

. prepare and submit a report to through each open head the Commission pursuant to spray / sprinkler header and Specification 6.3.A.1 withi-the verifying each open head next 30 days outlining ts

.ause spray / sprinkler nozzle is of inoperability, the ac*. ion unobstructed.

taken, and the plans for restoring the system to operable status.

4.

The provisions of Specification

- 1 3.0.A are not applicable.

D.

CO Systems D.

CO Systems-2 2

1.

The CO Storage Tank shs11 have 1.

At Icast once per 7 days the a minim,um standby level of 50 CO, Storage Tank' level and percent and a minimum pres-sure pressure will be verified, of.250 psig.

3.12/4.12-5 Amendment No. 114 m

h 7'

y t-treyi',

g--en---,------*-,"9 pw.g.---.p9

-*t.m,yge, m e 9pg-%w s.g p,-

g,,.

3-sN-Wewwem*Meywe'we-um-,e.'hsme+gnv.m+me m*

!'w4se--+eu=

    • 'si*-e*e vsmee++w-m-N'+-=8%

't

4 QUAD-Clll[5 DPR-29 2.

The CO Systems given in Table 2.

At least once per operating 2

3.12-3 shall be operable, cycle. the system valves and associated dampers will be veri-fled to actuate automatically and manually.

A brief flow test shall be made to verify flow from each nozzle, 3.

Specifiu.tions 3.12.0.1 and 3.12.D.2 above apply when the equipment in the areas given in Table 3.12-3 is required to be operable.

4.

With a CO System inoperable, 2

establish backup fire suppres-sion equipment for the unpro-tected area (s) within I hour and inspect the area t.< ice per shift.

5.

Restore the system i operable status within 14 days, or pre-l pare and submit a report to the Commission pursuant to I

Specification 6.3.A.1 within the next 30 days outlining the cause of inoperability, the action taken, and the plans and sche-dule for restoring the system to operable status.

6.

If actuated,the storage tank will be restored to greater than the minimum level within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.

7.

The provisions of Specification 3.0. A are not applicable.

3.12/4.12-6 Amendment No. 114

_. _ _ _. _ _.. _ _ _ _ _ _ _ _. _ _ _. ~. _ _ _. _ _... _. _ _

QUAD-C111ES DPR-29 E.

Fire Hose Stations E.

Fire Hose Stations 1

1.

The Fire Hose Stations given in 1.

At least once per 31 days, a Table 3.12-4 shall be operable visual inspection of each fire at all times when the equipment hose station shall be made to in the areas protected by the assure all equipment is avail-fire hose is required to be able at the station.

operable, 2.

With a hose station inoperable, 2.

At least once per operating route an-additional equivalent _

cycle, the hose will be removed capacity hose to the unprotected _

for inspection and reracked, area from an operable hose sta-Degraded gaskets in the coupi-tion within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, ings will be replaced.

3.

The provisions of Specification 3.

At least once per 3 years, each 3.0 A are not applicable, hose station valve will be par-tially opened to verify valve operab_ility and no blockage.

4.

At least once per 3 years a i

hydrostatic test will-be con-ducted on each hose at a pres-sure at least 50 psig greater than the maximum pressure avall-able at the hose station.

' F, Penetration Fire Barriers F.

penetration Fire Barriers 1.

All penetration fire barriers 1.

Each of the penetration fire protecting safety related. areas barriers shall be verified to be-shall be intact except as stated intact by visual inspection:

in Specification-3.12.F.2.

a.

At least once per operating cycle, and b.

pr:3r to declaring a pene-tration fire barrier func-tional following repairs or maintenance.

3.12/4.12-7 Amendment No. 114 l.

.-~--...

.-f.~.--.

- - - - - - - - " - - - - - - - - - - - - ~ - - ~ ~ - - ~ ~ ~ " ' ~ ~

i QUAD-CITIES DPR-29 2.

With one or more penetration fire barriers not intact, estab-lish a continuous fire watch on

.at least one side of the affected penetration within I hour if-the area on either side of the affected penetration con-tains equipment required to be operable.

3.

The provisions of Specification 3.0.A are not applicable.

G.

Fire Pump ilesel. Engine.

G.

Fire Pump Diesel Engine i

1..

The Fire Pump Diesel Engine 1.

The fire pump diesel starting-j shall be operable as specified 24 volt battery bank and che.rger i

in_3.12.B.I.a and 3.12.B.1.b.

shall be demonstrated OPERABLL:

_]

i a.

At least once per 7 days by verifying that:

i

1) The-electrolyte level of each battery is above the plates, and (2) The overall battery voltage is > 24 volts, b.

At least once per 92 days by verifying that the speci gravity is appropriate for continued service of battery.

c..At least once per 18 months by verifying that:
1) The batteries, cell plates ' and battery racks.

show no visual indication of physical damage or abnormal deterioration, and

2) The battery-to-battery 1

and terminal connet-tions are clean, tight, free of corrosion and coated with anti-corrosion material.

3.12/4.12-8 Amendment No. 114

. ~

QUAD C111[5 OPR 29 2.

The ftre pump diesel engine shall be demonstrated OPERABLL:

a.

At least once per 31 days by verifying:

1) The fuel storage day tank contains at least 150 gallons of fuel, and
2) The diesel starts from ambient conditions and operates for at least 20 minutes.

b.

At least once per 92 days by verifying f. hat a sample of diesel fuel from the fuel storage tank shall be checked for quality using existing station procedures for diesel oil in the main storage tanks.

c.

At least once per 18 months, during shutdown, by:

1) Subjecting the diesel to an inspection in accordance with pro-cedures prepared in conjunction with its manufacturer's recom-mendations for the class of service, and
2) Verifying the diesel starts from ambient conditions on the autostart signal and operates for > 20 minutes while~1oaded l

l with the fire pump.

l l

3.12/4.12-9 Amendment No. 114 l

QUAD 0111l5 DPR 29 3.12/4.12 LlH111NG COND1110NS FOR OPERA 110N AND

$URVElLLANCE REQUIREMEN15 BASES The operability of the fire suppression systems insures that adequate fire suppression capability is available to confine and extinguish fires occurrin0 in any port.fon of the facility where safety *related equipment is located.

The fire suppression system consists of the water system, sprinklers, 00,, and fire hose stations.

The collective capability of the fire suppression syltems is adequate to minimize potential damage to safety-related equipment, and is a major element in the facility fire protection program.

Operability of the fire detection instrumentation ensures that adequate warning capability is available for the prompt detection of fires.

This capability is required in order to detect and locate fires in their early stages.

Prompt detection of fires will reduce the potential for damage to safety-related equipment, and is an integral element in the overall facility fire protection program.

In the event that a portion of the fire detection instrumentation is inoperable, the establishment of frequent fire patrols in the affected areas is required to provide detection capability until the inoperable instrumentation is returned to service, in the event that portions of the fire suppression systems are inoperable, alternate backup fire fighting equipment is required to be made available in the affected areas until the affected equipment can be restored to service.

i A fire suppression water system shall consist of a water source, pumps, and distribution piping with associated valves.

Such valves shall include yard hydrant curb valves, and the first valve ahead of the water flow alarm device on each sprinkler or hose standpipe riser.

In the event that the fire suppression water system becomes inoperable, immediate corrective measures must be taken since this system provides the major itre suppression capability of the plant.

The requirements for a 24-hour report to the Commission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued protection of the nuclear plant.

The functional integrity of the penetration fire barriers ensures that fires will be confined or adequately retarded f rom spreading to adjacent portions of the facility.

This design feature minimizes the possibility of a $1ngle fire rapidly involving several areas of the f acility prior to detection and extinguishment.

The penetration fire barriers are a passive element in the facility fire protection program and are subject to periodic inspections.

l

\\

3.12/4.12-10 Amendment No. 114

4 6

QUADCll][5 DPR-29 1ABLE 3.12 2

$PRINKLlR $Y$1[M5 1.

Unit One Cable lunnel 2.

Unit One HPC1 Room 3.

Unit One Diesci Oil Day tank Room 4.

Unit 1/2 Diesel Oil Day lank Room 5.

Cable Spreading Room

^

TABLE 3.12 3 CO SYS1[MS 2

1.

Unit One Diesel Generator Area 2.

Unit 1/2 Diesel Ger.arator Area 3.

Unit One Diesel Oil Day lank Room 4.

Unit 1/2 Diesel Oil Day Tank Room l-l-

3.12/4.12-12 Amendment No. 114

QUAD-CITIES

^

OPR-29 TABLE 3.12-4 FIRE HOSE STATIONS NC.

SIZE LOCATION F168 100 ft.

Outside South Entrance to Control Room F169 100 ft.

Outside Cable Spreading Room F170 100 ft.

Outside Cable Spreading Room F111 100 ft.

Out=ide Battery Charger Room near MCC 15-1 F171 100 ft.

Outside Electrical Equipment Room F172 100 ft.

Outside Electrical Equipment Room near Machine Shop F129 100 ft.

Above Cable Tunnel at Column 17-G F130 100 ft.

Outside DG1 at column 23-G F156 100 ft.

Outside OG 1/2 at column 14-N r

F138 100 ft.

Outside RHR Service Water Pump rowns by column 18-D F158 100 ft.

South RHR Room F159 100 ft.

North RHR Room F160 100 ft.

Outs;de North Core Spray Room F161 100 ft.

Outside South Core Spray Room

  • CO-3B 150 ft.

Outside Battery Charger Room near MCC 18-2 l F142 100 ft.

Standby Liquid Control Area n

F143 100 ft.

Standby i; quid Control Area F106 100 ft.

Between Bus 13-1 and Bus 14-1

  • C -zA 150 ft.

South of Bus 14-1

  • r? 4L 150 ft.

Northwest of DG1 Room F155 100 ~t.

MCC 18/19-5 F151 100 ft.

Southwest of MCC 18-1A

  • These hose stations are not suoject to the surveillance requirements of Specification 4.12.E. and are instead operationally pressure tested annually.

4 4

1 12/4.1?-13 Amendment No. 116

SIGNIFICANT HAZARDS CONSIDERATIONS AND UNVIRC'! ~.. ENTAL ASSESSMENT EVALUATION Proposed Deletion of TS 3,12/4,12

' FIRE PROTECTION SYSTEMS" e

I 9

EVALUATJ_Q)] EQB BIGNIFICANT HAZARDS CONSIDERATION Proposed Deletion of Specification 3.12/4.12 Fire Protection Systems The proposed changes provided in this amendment repest are made in order to implement the recommendations of Generic Letters 88-12 and 86-10.

These changes have been reviewed by Commonwealth Edison Company and we believe that they do not present a Significant Hazards Consideration.

The basis for our determination is documented as follows:

BASIS EQB HQ SIGNIFICANT HAZARDS CONSIDERATION Commonwealth Edison has ovaluated this proposed amendment and determined that it involver no significant hazards consideration.

In accordance with the criteria of 10 CFR 50.92[c) a proposed amendment to an operating license involves no a:.gnificant hazards consideration if operation of the facility, in accordance with tho proposed amendment, would not:

1)

Involve a significant increase in the probability or consequences of an accident previously evaluated, because:

The proposed change to ret 've the Fire Protectjor. Technical Specifications does not involve a significant increase in the probability or consequences of an accident previously evaluated because the change doc 1 not involve a physical l

modification to the plant, a change to any safety system or a I

change to any setpoint.

The administrative concept of concurren.ly removing the fire protection reguirements from the Technical Specifications and incorporating these elements into the UFSAR does not affect the safety analysis presented in the Quad Cities UFSAR.

The changes will not affect the I

functioning of the fire protection program, which will be maintained pursuant to the operating license.

No changes will be made to the program that conflict with the requirements of the operating license.

2)

Create the possibility of a new or different kind of accident from any previously evaluated oecause:

The proposed changes to the Facility Operating License and the Technical Specifications represent an administrative shifting of responsibility for the Fire Protection Program Requirements from the Technical Specifications to the UFSAR.

The proposed changes do not affect the accident analysis or the operation or function of any safety-related equipment since the Fire Protection Program requirements will continue to be maintained.

No new modes of operation are introduced

  • these proposed changes.

Therefore, the proposed changes do not create the possibility of a new or different kind of accident

from any previously evaluated.

3)

Involve a significant reduction in the margin of safety because:

The deletion of the Fire Protection Technical Specifications and incorporation of these provisions into the UFSAR does not change the level of fire protection in the plant.

Additionally, controls added by the standard license condition and the 10 CFR 50.59 criteria will ensure future changes to the Fire Protection Program are properly evaluated.

Therefore, the proposed changes do not involve a significant reduction in the margin of safety.

ENVIRONMENTAL ASSESSMENT EVALUATION PROPOSED SPECIFICATION SECTION 3.12/4.12 FIRE PROTECTION SYSTEMS Commonwealth Edison has evaluated the proposed amendment in accordance with-the requirements of 10-CFR 51.21 and-has-determined that the amendment meets the' requirements for categorical-exclusion as specified by 10 CFR 51.22 (c) (9).

Conimonwealth Edison has determitmd that the amendment involves no significant hazards consideratisn, there is no significant change in the types or significant inc: aase -in the amounts of any effluent that may be released of fsite, and there is no significant

-increase in-' individual 1or cumulative occupational radiation exposure.

The proposed amendment-does not modify the existing facility and does not involve any new operation of the plant.

The: proposed deletion of the Fire Protection _ Technical Specifications and incorporation of these provisions into the UFSAR does-not change the level of_ fire protection in the_ plant.. As such, the proposed

-amendment does not involve any' change in the type or significant increases in effluents, or increase-individual or cumulative occupational-radiation exposure.-

l f

l l

- - ~ - -.

-i y;:7.-

q e-e

.l i

QC-1/ QC-2 DIFFERENCES I

-TS 3.12/4.12 FIRE PROTECTION SYSTEMS *

+

b 1

u e.iq pwn5g y

,wrwy

-a*-

-c a--a--

a 4 V e

--.5-r,rA,--s-+rw-+wi.,,

e.-

-4 c.

m

-m vs,9, e-.-

g

4 COMPARISON OF UNIT 1 AND UNIT 2 TECHNICAL BPECIFICATIONS l

FOR THE IDENTIFICATION OF TECHNICAL DIFFERENCES SECTION 3.12/4.12 FIRE PROTECTION Commonwealth Edison has conducted a comparison review of the-Unit 1 and Unit 2 Technical Specifications to identify any technical differences in support of combining the Technical Specifications into one document.

The intent of the raview was not to identify any differences in presentation style (e.g. table formats, use of capital letters, etc.) or punctuation but rather to identify areas which the Technical Specifications are technically or administratively different.

The review of Section 3.12/4.12, " Fire Protection" revealed the following technl cal differences:

Pace 3.12/4.12-5

_ Unit 1 Technical Specification 3.12.C.2 states, "With a sprinkler system inoperable, establish backup fire suppression equipment and inspect the area twice per shift."

The Unit 2 Tecnnical Specification 3.12.C.2 statas, "With the cable tunnel sprinkler system inoperable, establish a continuous fire-watch with backup fire suppression eguipment for the unprotected area witnin one hour" and Specification 3.12.C.3 states, "With any other sprinkler system inoperable, establish backup fire suppression within one hour and inspect the-area.twice per shift."

Unit 1 Technical Specification 3.12.C.2 does not establish a time to establish backup fire suppression equipment while Unit 2 specifies a one hour period.

Based on our historical review of our submittals and NRR approval, the time allowance was proposed for both units but inadvertently omitted in the final approval process.

A continuous fire watch is required only for an inoperable sprinkler system in the Unit 2 cable tunnel.

The Unit--I cable tunnel has redundant back-up equipment separate from this area and a twice per shift inspection was deemed acceptable for the Unit 1 cable (

Reference:

G.

Lear to Cordell Reed letter dated March 22, 1978)

.m

-c, 1

i

. Thexfollowing administrative differences were

- identified:

d Eagt.1.,Jjt / 4.12-4

- 4.12.C Unit 1: ' flow-path through at least one complete 9

Unit 2: flew path through at least once complete Page-3.12/4.12-6

- 3;12.D.3.

-Unit'1:1given.in Table 3.12-3

?

- Unit 2:'given in Table-3.12.3 Page 3.12/4.12-10.

Paragraph 5-Unit _1:

The requirements for a 24-hour Unit 2:- The requirement for a 24-hour fr s

I

,v,,

w war-e n-e---,,

-a,we,

,e

-v.,

-n--gweu

,e,e

.w-

,-re--