ML20078P946

From kanterella
Jump to navigation Jump to search
Second Interim Deficiency Rept Re Failure to Specify IEEE Class on Procurement Specs on Crane Co Valves.Initially Reported on 830509.Procurement of Replacement Equipment Initiated.Next Rept Will Be Submitted by 840820
ML20078P946
Person / Time
Site: Bellefonte  Tennessee Valley Authority icon.png
Issue date: 11/04/1983
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8311090286
Download: ML20078P946 (2)


Text

TENNESSEE VALLEY AUTHORITY CH ATTANOOG A. TENNESSEE 37401 8)%V7 400 Chestnut Street Tower II 4 8 *. 8t/

November 4,1983 BLRD-50-438/83-34 BLRD-50-439/83-30 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - FAILURE TO SPECIFY IEEE CLASS ON PROCUREMENT SPECIFICATIONS - BLRD-50-438/83-34, BLRD-50-439/83 SECOND INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector Linda Watson on May 9, 1983 in accordance with 10 CFR 50.55(e) as NCR BLN EEB 8307. Since that time related NCR BLN BLP 8324 has been reported and will be handled jointly with NCR BLN EEB 8307. This was followed by our interim report dated June 9,1983 Enclosed is our second interim report. We expect to submit our next report by August 20, 1984.

If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY N

L. M. Mills, nager Nuclear Licensing Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Records Center (Enclosure)

Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 8311090286 831104 DR ADOCK 05000 1

d ggacW-1983-TVA SOTH ANNIVERSARY g

~

fd An Equal Opportunity Employer

, & P --/

ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 FAILURE TO SPECIFY IEEE CLASS ON PROCUREMENT SPECIFICATIONS BLRD-50-438/83-34, BLRD-50-439/83-30 10 CPR 50.55(e)

NCRs BLN EEB S307 AND BLN BLP 8324 SECOND INTERIM REPORT Description of Deficiency Limit switches, control valves, and solenoid valves for safety-related systems which are required to be class 1E components, were procured from Crane Company (Chempump Division), Yarway Corporation, Copes-Vulcan Corporation, and Masoneilan Valve Corporation without specifying the proper IEEE class. Because of this inadvertent error, documentation necessary to verify the class of these components was not provided.

Interim Progress The supplier (s) of the equipment affected by this condition have been contacted by TVA's Electrical Engineering Support Branch (EEB) to see if the necessary documentation to permit the use of this -equipment in

~

class 1E applications could be obtained. With the exception of two valvea supplied by Yarway Corporation, this documentation is not available. Procurement of replacement equipment by EEB has been initiated. TVA will provide the NRC with further information in our next report.

i e

l i

i l

.-