DESIGN FEATURES 5.3 REACTOR CORE FUEL ASSEMBLIES 5.3.1 The reactor core shall contain 217 fuel assemblies with each fuel assembly containing a maximum of 236 fuel rods cicd with Zircaloy-4.

Each fuel rod shall have a nominal active fuel length of 150 inches and contain a nominal total weight of 1807 grams uranium.

The initial core loading shall have a maximum enrichment of 2.91 weight percent U-235.

Reload fuel shall be similar in physical design to the initial core loading and shall have a maximum enrichment of 4.1 weight percent U-235.

I CONTROL ELEMENT ASSEMBLIES 5.3.2 The reactor core shall contain 83 full-length and 8 part-length control element assemblies.

5.4 REACTOR COOLANT SYSTEM f

DESIGN PRESSURE AND TEMPERATURE

'5.4.1 The Reactor Coolant System is designed and shall be maintained:

~

a.

In accordance with the code requirements specified in Section 5.2 of the FSAR with allowance for normal degradation pursuant of the applicable Surveillance Requirements, b.

For a pressure of 2500 psia, and c.

For a temperature of 650'F, except for the pressurizer and surge line which is 700*F.

VOLUME 5.4.2 The total water and steam volume of the reactor coolant system is 11,800

+600, -0 cubic feet-at a nominal T,yg of 582.1*F.

5.5 METEOROLOGICAL TOWERS LOCATION 5.5.1 The primary and backup meteorological towers shall be located as shown on Figure 5.1-1.

WATERFORD - UNIT 3 5-5 AMENDMENT NO. 7,##

9502010314 950127 PDR ADOCK 050003B2 P

PDR

(---

1 9

y I ~ '.

c NPF-38-163 ATTACHMENT II

,+

31 DESIGN FEATlRES i

'5.3 REACTOR CORE i

FUEL ASSEMBLIES 5.3.1 The reactor core shall contain 217 fuel assemblies with each fuel. assembly containing a maximum of 236 fuel rods clad with Zircaloy 4.

Each fuel rod shall have a nominal active fuel length of 150 inches and contain a nominal total weight of 1807 1830 grams uranium.

l The initial core loading shall have a maximum enrichment of 2.91 weight percent U-235.

Reload fuel shall be similar in physical design to the initial core loadingg-and Assemblies shall have a maximum enrichment of Art 4.9 weight percent U-235 provided they contain sufficient fixed poisons to meet the final storage requirements described in section 5.6.

CONTROL ELEMENT ASSEMBLIES 5.3.2 The reactor core shall contain 83 full-length and 8 part-length control element f

assemblies.

5.4 REACTOR COOLANT SYSTEM DESIGN PRESSURE AND TEMPERATURE

)

5.4.1 The Reactor Coolant System is designed and shall be maintained-a.

In accordance with the code requirements specified in Section 5.2 of the FSAR l

with allowance for normal degradation pursuant of the applicable Surveillance j

Requirements, j

l b.

For a pressure of 2500 psia, and 1

i c.

For a temperature of 650F, except for the pressurizer and surge line which is I

700*F.

l VOLUME 5.4.2 The total water and steam volume of the reactor coolant system is 11.800 +600, -0 cubic feet at a nominal Tavg of 582.1*F.

i 5.5 METEOROLOGICAL TOWERS LOCATION 5.5.1 The primary and backup meteorological towers shall be located as shown on Figure 5.1-1.

WATERFORD - UNIT 3 55 AMENDMENT NO.,44

.a i

NPF-38-163 ATTACHMENT III