e U-0662 Blinois Power Company
$!2$(c9-08)L 500 SOUTH 27TH STHEET, P. O. BOX 511, DECATUR, ILLINOIS 62525-1805 Docket No. 50-461 September 8, 1983 s
Director of Nuclear Reactor Regulation Attention:
Mr. A. Schwencer, Chief Licensing Branch No. 2 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C.
20555 Subj ect :
Clinton Power Station Unit 1 Post Fire Emergency Lighting
Dear Mr. Schwencer:
References:
1)
SER 9.5.3, Emergency Lighting (page 9-30)
(NUREG-0853).
2) 10 CFR 50 Appendix R, Section III, paragraph j,
Fire Protection Program for Nuclear Power Facilities Operating Prior to 1/1/79, Specific Requirements, Emergency Lighting.
3)
Standard Review Plan 9.5.1, Section C, Subsection 4, paragraph e.
Fire Protection Programs, Positions, General Plant Guidelines, Lighting and Communication (page 9. 5.1-31).
4)
IP letter dated 12/16/82, (U-0586), G.
E. Wuller to A. Schwencer, NRC.
Reference 1 states that Illinois Power (IP) will meet the emergency-lighting requirements of reference 2 by installing 8-hr. battery pack lighting units in all areas needed for operation of safe shutdown equipment and in access and egress routeo.
In the reference 4 submittal, IP requested an exemption from the reference 2 requirements because the Clinton Power Station has lighting fed from lE sources in the required areas.
Recent telephone conversations with Messrs. J. Stang and H. Abelson of NRC Staff have led to a change in our emergency lighting system and an exemption to the 10 CFR 50 Appendix R requirements is not needed.
f00h
'9 8309130108 830908 PDR ADOCK 05000461 E
?!
U- 0662 B51-83 (09 - 08)-L September 8, 1983 Page 2 The'Clinton Power Station will meet the emergency lighting requirements as stated in the above references for post fire-conditions.
Specifically, fixed, self-contained lighting fixtures with individual battery power supplies with a minimum of 8 hrs. of capacity will be provided in all areas that must
- be manned for safe shutdown and for access and egress routes thereto.
At the Clinton Power Station the areas needed for safe shutdown are:
1)
Main Control Room 2)
Remote Shutdown Panel: (C61-P001) 3)
NSPS Power Distribution Panels (C71-P001A/B) 4)
Diesel Generator lA Local Control Panels (lPL12JA).
Please let us hear from you soon if you have any questions on this matter.
Sincerely,
.-Nelson Director-Nuclear Licensing and Configuration Management Nuclear Station Engineering ALR/GEW/lt.
attachment cc:
H. Abelson, NRC Clinton Licensing Proj ect Manager J. E. Stang, Jr., NRC CHEB H. H. Livermore, NRC Senior Resident Inspector Illinois Department of Nuclear Safety