ML20077C717

From kanterella
Jump to navigation Jump to search
Issue 9 to FPOR-14, Fire Protection Operability Requirements
ML20077C717
Person / Time
Site: Fort Saint Vrain 
Issue date: 11/30/1994
From:
PUBLIC SERVICE CO. OF COLORADO
To:
References
FPOR-14, NUDOCS 9412060302
Download: ML20077C717 (5)


Text

_ _ - -

FORT ST. VRAIN NUCLEAR GENERATING STATION Public j $0fVICOs PUBLIC SERVICE COMPANY OF COLORADO

(

O

~

ooCUMENT TRANSMITTAL To

_ Document _ Control _Dack DATE

__11 -3 0-9_4 FROM Debbie Russell Public Service Compa.ny_of_G.oloradp - FSV

_1680LWCA_191 l

1 Plat.teville, CO 80651 THE FOLLOWING MATERIAL IS TRANSMITTED HEREWITH:

FPOR index, issue 22 dated 11-8-94 FPOR 14 issue 9 b

O CGuo~

00b 9412060302 941130 p

O PDR ADOCK 05000267 l

F PDR PLEASE RETURN YOUR SIGNED ACKNOWLEDGEMENT INDICATING RECEIPT OF THE ABOVE MATERIAL

.. u,~, o,

,ou,,

Fo'en tC1372 22 3374 INill Al OR Iornard Wh'te Copy to Re,apient. Petain Yehow Copy RECIPILNT Return Ac knowledged Whete Copy to inmatoi

Dz'22 11-08-94 Issuo 22 i

SECTION DFP.S.1 FIRE PROTECTION OPERABILITY REOUIREMENTS TABLE OF CONTENTS NUMBER TITLE ISSUB EFFECTIVE DATE FPOR-0 Fire Protection Operability 4

12-7-92 FPOR-1 Emergency Diesel Generator Carbon 4

12-7-92 Dioxide System FPOR-2 Carbon Dioxide Hose Reels -

4 12-7-92 DELETED FPOR-3 Halon Systems 5

12-7-92 FPOR-4 Deluge Spray Systems 3

12-7-92 FPOR-5 Fixed Water Spray Systems 4

12-7-92 FPOR-6 Plant Yard Hydrants 3

12-7-92 FPOR-7 Fire Extinguishers 4

12-7-92 FPOR-8 Breathing Air System - DELETED 3

12-7-92 FPOR-9 Fire Hose Stations 4

12-7-92 FPOR-10 Fire Water Pumps 4

12-7-92 FPOR-11 Fire Water Headers and Mains 3

12-7-92 FPOR-12 Fire Detectors 6

12-7-92 j

FPOR-13 Fire Barriers 7

12-7-92 FPOR-14 Fire Doors 9

11-8-94 FPOR-15 Fire Dampers 5

12-7-92 FPOR-16 Fire Protection Cooldown Trains -

5 12-7-92 DELETED FPOR-17 Alternate Cooling Method (ACM) 5 12-7-92 DELETED FPOR-18 Ladders - DELETED 4

12-7-92 FPOR-19 Cable Wraps - DELETED 3

12-7-92 FPOR-20 Emergency Lighting - DELETED 4

12-7-92 FPOR-21 Site Fire Brigade - DELETED 2

12-7-92 FPOR-22 Storage of Activated Graphite -

2 10-12-94 DELETED FPOR-23 Fire Water Makeup System 3

10-12-94

FPOR-14 Issuo 9 Page 1 of 3 FIhE PROTECTION OPERABILITY REOUIREMEIMS Fire Doors FPOR-14 The fire doors listed in Table FPOR-14-1 shall be operable.

APPLICABILITY:

At all times.

ACTIONS:

With one or more of the required fire doors inoperable, within i hour, establish an hourly fire watch on at least one side of the affected door (s),

l EXCEPTION: Fire doors may be opened for brief periods (i.e.,

I personnel and equipment access and egress, not to exceed 60 minutes) without taking the actions described above. However, for fire doors which will be open for longer periods of time, the aforementioned actions apply.

SURVEILLANCE REOUIREMENTS:

The required fire doors shall be demonstrated operable:

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, by verifying each fire door is a.

closed.

l b.

At least once per quarter (92 days) or following maintenance work on the door by:

1)

Functionally testing and visually inspecting each fire door, and replacing any damaged hardware (i.e., hinges, latches, catches, closers, etc.).

2)

Verifying combustible materials are not stored near the door and the door opening is not obstructed.

l c.

Deleted O

FPOR-14 Iccus 9 Page 2 of 3 BASIS FOR FPOR-14:

The operability of the fire doors ensures that fire damage will be limited, as analyzed in the DFPP. These design features minimize the possibility of a single fire involving more than one fire area prior to detection and extinguishment.

In the event that a fire door does not remain intact, a fire watch on one side of the affected door will ensure early notification of a fire.

Verifying the position of each fire door at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> ensures that the fire doors are in their as-designed condition to confine or retard fires from spreading to adjacent portions of the facility.

Visually inspecting and functionally testing each fire door at l least once per quarter, and following maintenance or repair work, ensures closing mechanisms, latches, hinges, and catches will be l able to perform their design function when required.

Maintaining the immediate door area free of combustibles and obstructions helps ensure free operation of the door and reduce the possibility of fire spread from one area to another.

r~%

kl National Fire Protection Association (NFPA) 80 - Standard for Fire m

Doors and Fire Windows and the NFPA Fire Protection Systems Inspection, Test & Maintenance Manual was used as a guide for the frequencies and requirements defined in this FPOR.

OG

FPOR-14 Iccus 9-Pcg3 3 of 3 TABLE: FPOR-14-1 DOOR.#

ELEVATION NAME 76 4791 Aux Boiler South Doors 77 4791 Aux Boiler East Doors 79 4791 Diesel Generator Room, West Door, North End 80 4791 Diesel Generator Room, Dividing Wall, North End 81 4791 Diesel Generator Room, Dividing Wall, South End 82 4791 Diesel Generator Room, East Door, North End 91 4792'-10" Turbine Lube Oil Storage Room 94 4792'-7" Turbine Lube 011 Reservoir Room 142 Electric Fire Water Pump Room RSD 1 4789'-6" Records Center West Do RSD 7 4790'-2" Records Center East Door i

RSD 8 4790'-2" Records Center East Door l

l I

i O