ML20076H099

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Containment Spray/Rhr Motor Oil Foaming.Foaming Observed in Oil Sight Gauges Determined to Be Normal.Condition Not Reportable Per 10CFR50.55(e)
ML20076H099
Person / Time
Site: Wolf Creek 
Issue date: 06/10/1983
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, KMLNRC-83-069, KMLNRC-83-69, NUDOCS 8306160415
Download: ML20076H099 (1)


Text

-

KANSAS CAS AND ELECT. lC COMPANY TPE FLECTF#C COMPANY

@LENN L M O E S T E ft vga passioemt. muctsee June 10, 1983 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 U.S. Nuclear Regulatory Commission Region IV Q

{g

((g]

611 Ryan Plaza Drive, Suita 1000

  • }

1 Arlington, Texas 76011 f

UljNI31983 4L nI)\\

KMLNRC 83-069 L. -

Re:

Docket No. STN 50-482 I

Subj: Withdrawal of Potential 10CFRf 0.55(e)

Containment Spray /RHR Motor Oil Foaming

Dear Mr. Seidle:

On May 12, 1983, Mr. Michael D. Hall of Kansas Gas and Electric Company (KG&E) reported a potential 10CFR50.55(e) issue concerning oil foaming in the contain-ment spray pump and residual heat removal (RHR) pump motors to Mr. Johns Jaudon of the Nuclear Regulatory Commission, Region IV.

Subsequent evaluation of this matter has revealed that a safety concern does not exist.

This initial concern developed while running a containment spray pump motor and foaming was observed in the oil sight gauge. The RHR trators are of a similar design and were therefore included in the initial reporting of this matter even though they had not been run.

A Westinghouse field engineer has since monitored a test run of the same motor and verified that the degree of foaming being observed is normal and riot excessive for this type of motor and sfght glass arrangement.

KG&E has concluded that a significant deficiency does not exist and that this matter is not reportable pursuant to 10CFR50.55(e). Documentation concerning the evaluation of this issue will be maintained by KGEE and is available for your review. Please direct any further questions concerning this subject to me or to Mr. Otto Maynard of my staff.

Yours very truly, Y

ll1 GLK:bb cc: RCDeYoung HRoberds/WSchum 8306160415 830610 PDR ADOCK 05000482

]6 -y S

PDR of0 201 N. Market - Wichita, Kansas - Mail Address: PO. Box 208 I #chsta. Kansas 67201 - Telephone: Area Code (316) 261-6451

KANSAS GAS AND ELECTRIC COMPANY THE ELECTAC COMPmNY

@LENN L MOESTER vec s possion%t - esvCLsse June 10, 1983 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 U.S. Nuclear Regulatory Commission

}.]

{g]

Region IV 611 Ryan Plaza Drive, Suite 1000 i

Arlington, Texas 76011

!s N

h i UUN I 3 l983 h

! \\l KMLNRC 83-069

_. t Re:

Docket No. STN 50-482 Subj: Withdrawal of Potential 10CFR50.55(e) -'

Containment Spray /FHR Motor Oil Foaming

Dear Mr. Seidle:

On May 12, 1983, Mr. Michael D. Hall of Kansas Gas and Electric Company (KG&E) reported a potential 10CFR50.55(e) issue concerning oil foaming in the contain-ment spray pump and residual heat removal (RHR) pump motors to Mr. Johns Jaudon of the Nuclear Regulatory Commission, Region IV.

Subsequent evaluation of this matter has revealed that a safety concern does not exist.

This initial concern developed while running a containment spray pump motor and foaming was observed in the oil sight gauge. The RHR motors are of a similar design and were therefore included in the initial reporting of this matter even though they had not been run. A Westinghouse field engineer has since monitored a test run of the same motor and verified that the degree of foaming being observed is normal and not excessive for this type of motor and sight glass arrangement.

KG&E has concluded that a significant. deficiency does not exist and that this matter is not reportable pursuant to 10CFR50.55(e). Documentation concerning the evaluation of this issue will be maintained by KG&E and is available for your review, Please direct any further questions concerning this subject to me or to Mr. Otto Maynard of my staff.

Yours very truly, fl,h -

h GLK:bb cc: RCDeYoung HRoberds/WSchum 8306160415 830610 PDR ADOCK 05000482

]6.2,7 S

PDR i[0 201 N. Market - Wichita, Kansas - Mail Address: PO. Box 208 I Wichita, Kansas 67201 - Telephone: Area Code (316) 261-6451

... J