Rev 1 to OL Change Request 176,dtd 910419,reducing Overpressure Protection Sys Setpoint by 4 Psig to 440 Psig, Based on Results of WCAP-12966 Re Steam Generator Tube Plugging Analysis Program
ML20076D896
Person / Time
Site: Beaver Valley
Issue date: 07/25/1991
From: Sieber J
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20076D897 List:
References
TAC-76889, NUDOCS 9107310001
Download: ML20076D896 (1)


Text

1 A f $ Py hf NU a l M hO

%t pngtert. PA 1507/ 6 04 Kn*H D 54 Of *\\

we.n, w.a<ne nw '

July 25, 1991 U.

S.

Nuclear Regulatery Commission Attn:

Document Control Desk Washington, DC 20555

Subject:

Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 Operar,ing License Change Request No. 176 Revision 1 Modification (TAC No. 76889)

The purpose of this letter is to provide a modificatinn to ope rat i r.-

License Change Request No. 176, dated April 19, 1991.

That request proposed a

change to the overpressure protection system (OPpS) setpoint from 350 psig to 444 psig.

Attached is a

modification to reduce the OPPS setpoint by 4 psig to 440 psig based on the results of WCAP-12966 (Duquesne Light Company, Beavor Valley Power Station Units 1 & 2, 20 Percent Steam Generator Tube Plugging Analysis

Program, Engineering and Licensing Report).

.This modification has been discussed with our NRC Project Manager and is provided to document the change to the proposed Technical Specification amendment.

The previously submitted Attachment B

(Safety Analysis and No Significant Hazard Evaluation) remains applicable for this nodification.

This submittal provides a more conservative setpoint in accordance with WCAP-12966 which was reviewed and approved by the Onsite Safety Committee (OSC, and Offsite Review Committee (ORC).