ML20074B074

From kanterella
Jump to navigation Jump to search
Forwards Draft Change to FSAR Section 9.2.6.4.2.2 Re Spray Pond Natural Evaporation Per 830420 Telcon.Change to Be Formally Incorporated Into FSAR Rev Scheduled for June 1983
ML20074B074
Person / Time
Site: Limerick  Constellation icon.png
Issue date: 05/13/1983
From: Bradley E
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Schwencer A
Office of Nuclear Reactor Regulation
References
NUDOCS 8305180402
Download: ML20074B074 (3)


Text

h 4

A PFilLADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 PHILADELPHIA. PA.19101 CDW ARD G. S AUER, J R.

N MMN vecE rassioEnv ANo SENER AL COUNsEb EJG EN E J. BR ADLEY assOcs ATE SENER AL COUNsEh DON ALD BLANKEN EUDOLPH A. CHILLEMI

[

p E. C. KIR K H A LL T. H. M AHER CORNELL PAUL AUERBACH Assistant SEnEn AL counse6 EDW ARD J. CULLEN, JR.

THOM AS H. MILLER, J R.

IREN E A. McKENN A ASSISTANT CouMSEL Mr. A. Schwencer, Chief Licensing Branch No. 2 Division of Licensing U. S. Nuclear Regulatory Commission h'ashington, DC 20555

Subject:

I.imerick Generating Station, Units 1 and 2 upen Item from the Ilydrologic 5 Geotechnical Engineering Branch (ilGEB)

Dear Mr. Schwencer:

The attached draft change to FSAR Section 9.2.6.4.2.2 is being made as a result of a telephone conversation with Mr. Martin of your staff and Mr. h'escott of IIGEB on April 20, 1983.

This draft change will be formally incorporated into the FSAR revision scheduled for June,1983.

Sincerely, I

I Euge e J. Bradley JTR/ cam d/16 00/

cc: See Attached Service List 8305180402 830513 1

PDR ADOCK 05000352 A

PDR l

jr cc: Judge Lawrence Brenner

'(w/o enclosure)

. Judge Richard F. Cole (w/o enclosure)

Judge Peter A. Morris (w/o enclosure)

Troy B. Conner, Jr., Esq.

(w/o enclosure)

Ann P. Ilodgdon (w/o enclosure)

Mr. Frank R. Romano (w/o enclosure)

Mr. Robert L. Anthony (w/o enclosure)

Mr. Marvin I. Lewis (w/o enclosure)

Judith A. Dorsey, Esq.

(w/o enclosure)

Charles W. Elliott, Esq.

(w/o enclosure)

Mr. Alan J. Nogee (w/o enclosure)

Thomas Y. Au, Esq.

(w/o enclosure)

Mr. Thomas Gerusky (w/o enclosure)

Director, Pennsylvania Emergency Management Agency (w/o enclosure).

Mr. Steven P. Hershey (w/o enclosure)

James M. Neill, Esq.

(w/o enclosure)

Donald S. Bronstein, Esq.

(w/o enclosure)

Mr. Joseph H. White, III (w/o enclosure)

Walter W.-Cohen, Esq.

(w/o enclosure)

Robert J. Sugarman, Esq.

(w/o enclosure)

Rodney D. Johnson (w/o enclosure)

Atomic Safety and Licensing Appeal Board (w/o enclosure)

Atomic Safety and Licensing Board Panel (w/o enclosure)

Docket and Service Section (w/o enclosure)

m o

Replace existing Section 9.2.6.4.2.2 with the fo1100ing:

9.2.6.4.2.2 Natural evaporation of the Spray Pond was based on the meteorology selected in accordance with Regulatory Guide 1.27, Revision 2, and a-constant pond surface area of 9.6 acres. The water loss due to natural evaporation is shown in Table 9.2-13.

This is conservative since the average surface area over the 30-day accident scenario is-less than 9.6 acres, and the effect of the sprays suppressing evaporation is not taken into account.

The evaporation calculation was based on the methodology of Reference 9.2-5.

REFERENCE 9.2-5 Ryan, P. J., and Harleman, D.R.F. "An Analytical and Experimental Study of Transient Cooling Pond Behavior", Ralph M. Parsons Laboratory for Kater Resources and Hydrodynamics, Report No. 161, MIT Press, January,1973.

JTR/ cam c/1 1

4

.