ML20074A310

From kanterella
Jump to navigation Jump to search
Part 21 Rept Re Defect in Shielded Multiconductor Cable Installed in HVAC Control Panels.Mcc Powers Personnel Attached Hold Tags to 13 HVAC Control Panels W/Defect. Evaluation Being Conducted
ML20074A310
Person / Time
Site: Clinton, LaSalle, 05000000
Issue date: 05/04/1983
From: Hall D
ILLINOIS POWER CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20074A311 List:
References
REF-PT21-83-886-000 1606-L, PT21-83-886, PT21-83-886-000, U-10053, NUDOCS 8305120475
Download: ML20074A310 (2)


Text

e e

1606-L ILLINOIS POWER OOMPANY y-10053 CLINTON POWER STATION. P.O. BOX 678. CLINTON. ILLINOIS 61727 May 4, 1983 Docket No. 50-461 Mr. James G. Keppler Regional Administrator, Region III U.

S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 Subj ect:

10CFR Part 21 Defect in Shielded Multiconductor Cable Installed In HVAC Control Panels at Clinton Power Station

Dear Mr. Keppler:

In Illinois Power letter to Mr. Frank Jablonski, NRC Region III, (Ref: U-10024, 1606-L, dated January 17, 1983) Illinois Power agreed to notify Region III of those 10CFR Part 21 defects that affect Clinton Power Station and that were previously re-ported to the Commission by vendors or contractors.

In accordance with that agreement, the following information is submitted:

On April 18, 1983, Mr. Guy Fauconneau, Vice President of MCC Powers, 5440 West Fargo Avenue, Skokie, Illinois

60777, l

informed the NRC Office of Inspection and Enforcement, Washington, l

DC, of a defect affecting Clinton Power Station (copy attached).

I MCC Powers has determined that a construction defect exists in shielded multiconductor cable installed in HVAC control panels l

supplied by MCC Powers.

The report to the Commission states that I

the insulation of individual conductors has been damaged by cut-l ting too deeply to remove the covering material.

MCC Powers personnel at Clinton Power Station have attached

" Hold" tags to the thirteen (13) HVAC Control panels associated with this problem.

i MAY 61983 c

$EE"EE00*o8888jL h

PDR

James G. Keppler May 4, 1983 NRC Page 2 of 2 Illinois Power Company is conducting an evaluation of the reported condition and will assure that corrective action is taken to resolve the problem.

Si erely yours,

. P. Hall Vice President KFH/rdc Attachment cc:

H. H. Livermore, NRC Resident Inspector Illinois Department of Nuclear Safety Manager - Quality Assurance Director of Inspection and Enforcement (3 copies)

INPO Records Center

~

1 e

l.._

_ _ _ _ _ _ _ _, _ _.