e e
1606-L ILLINOIS POWER OOMPANY y-10053 CLINTON POWER STATION. P.O. BOX 678. CLINTON. ILLINOIS 61727 May 4, 1983 Docket No. 50-461 Mr. James G. Keppler Regional Administrator, Region III U.
S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 Subj ect:
10CFR Part 21 Defect in Shielded Multiconductor Cable Installed In HVAC Control Panels at Clinton Power Station
Dear Mr. Keppler:
In Illinois Power letter to Mr. Frank Jablonski, NRC Region III, (Ref: U-10024, 1606-L, dated January 17, 1983) Illinois Power agreed to notify Region III of those 10CFR Part 21 defects that affect Clinton Power Station and that were previously re-ported to the Commission by vendors or contractors.
In accordance with that agreement, the following information is submitted:
On April 18, 1983, Mr. Guy Fauconneau, Vice President of MCC Powers, 5440 West Fargo Avenue, Skokie, Illinois
- 60777, l
informed the NRC Office of Inspection and Enforcement, Washington, l
DC, of a defect affecting Clinton Power Station (copy attached).
I MCC Powers has determined that a construction defect exists in shielded multiconductor cable installed in HVAC control panels l
supplied by MCC Powers.
The report to the Commission states that I
the insulation of individual conductors has been damaged by cut-l ting too deeply to remove the covering material.
MCC Powers personnel at Clinton Power Station have attached
" Hold" tags to the thirteen (13) HVAC Control panels associated with this problem.
i MAY 61983 c
$EE"EE00*o8888jL h
James G. Keppler May 4, 1983 NRC Page 2 of 2 Illinois Power Company is conducting an evaluation of the reported condition and will assure that corrective action is taken to resolve the problem.
Si erely yours,
. P. Hall Vice President KFH/rdc Attachment cc:
H. H. Livermore, NRC Resident Inspector Illinois Department of Nuclear Safety Manager - Quality Assurance Director of Inspection and Enforcement (3 copies)
INPO Records Center
~
1 e
- l.._