ML20072P947

From kanterella
Jump to navigation Jump to search
Application for Amend to License DPR-59,altering Table of Values Specifying Min Critical Power Ratio Operating Limits for Incremental Cycle Core Average Exposure
ML20072P947
Person / Time
Site: FitzPatrick 
Issue date: 03/30/1983
From: Bayne J
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
Shared Package
ML20072P929 List:
References
NUDOCS 8304040425
Download: ML20072P947 (1)


Text

BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION In the Matter l

1 POWER AUTHORITY OF THE STATE OF NEW YORK l

Docket No. 50-333 I

James A.

FitzPatrick Nuclear Power Plant l

APPLICATION FOR AMENDMENT TO OPERATING LICENSE Pursuant to Section 50.90 of the regulations of the Nuclear Regulatory Commission, the Power Authority of the State of New York, as holder of Facility Operating License No. DPR-59, hereby applies for an Amendment to che Technical Specifications contained in Appendix A of this license.

The propcsed Technical Specification changes alter the table of values specifying Minimum Critical Power Ratio (MCPR) operating limits for incremental cycle core average exposure in Section 3.1.B.l.

Accordingly, Figures 3.1-2 a, b and c, depicting MCPR operating limit versus scram time ratio, are revised to reflect the new limits.

Thet changes correct the original Cycle 5 MCPR limits, which were found to be slightly non-conservative for pressurization transients due to the use of an improper carryunder fraction by General Electric Company in its imput data for the ODYN computer code.

The proposed changes to the Technical Specifications are Attachment I to this applcation.

The Safety Evaluation for this change is included as Attachment II.

POWER AUTHORITY OF THE STATE OF NEW YORK By) N

_%!w__

Executive Vic) President

~ Bayne (21/ P.

e Nuclear Generation State of New York County of Westchester Subscribed and Sworn to before me this yo 4 day of Men t,

1983.

s fMITCHELL 1 P'M ?.TM f!ct ui iT,. 's# = < ! i ' : w Y x' tm De b.19N it /[G tb Cc 1 o

.I h rh

'/ / Notary Public 8304040425 830330 PDR ADDCK 05000337 P

PDR t