Docket No. 50-423 B14943 Millstone Nuclear Power Station, Unit No. 3 Proposed Revision to Technical Specifications Ultimate Heat Sink Marked-up Page August 1994 9409020276 940819 PDR ADOCK 05000423 P

PDR

PLANT SYSTEMS gg,.,,,

3,,,7

]

n ua evow 3/4.7.5 ULTIMATE HEAT SINK

.~

LIMI.ING CONDITION FOR OPERATION l

3.7.5 The ultimate heat sink shall be OPERABLE with an average water tempera-ture of less than or equal to 75*F at the Unit 3 intake structure.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

With the requirement o the abov specification not satisfied, be in at least HOT STANDBY within 6 COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS i

4.7.5 The ultimate heat sink shall be determined OPERABLL:

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying the average water temperature a.

at the Unit 3 intake structure to be within limits.

At least once per 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> by verifying the average water temperature b.

at the Unit 3 intake structure to be within limits when the average water temperature exceeds 70*F.

4 g citua w

  • L o pen =4 b- %r aq q, 40 m q iq, H 01 ST*@H cond.hb J.Il be 24 %vs h.k W.s p elod,

3

+o nach a

'rf 4h 4cmpencbre m creme <- abwe U "F, be in N OT % O 6y w M n Hlu v'ief + (o hou<s,

j MILLSTONE - UNIT 3 3/4 7-13 b WULM*^4 Mo.

Docket No. 50-423 B14943 Millstone Nuclear Power Station, Unit No. 3 Proposed Revision to Technical Specifications Ultimate Heat Sink Retyped Page August 1994 1

l l

PLANT SYSTEMS 3/4.7.5 ULTIMATE HEAT SINK LIMITING CONDITION FOR OPERATION 3.7.5 The ultimate heat sink shall be OPERABLE with an average water tempera-ture of less than or equal to 75'F at the Unit 3 intake structure.

l APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

With the requirement of the above specification not satisfied, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

  • and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i SURVEILLANCE REQUIREMENTS i

4.7.5 The ultimate heat sink shall be determined OPERABLE:

a.

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying the average water temperature

~;

at the Unit 3 intake structure to be within limits.

f b.

At least once per 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> by verifying the average water temperature at the Unit 3 intake structure to be within limits when the average water temperature exceeds 70'F.

I i

  • For a period from August 1994 to October 1,1994, the allowed time to reach a H0T STANDBY condition wfTT,be 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. During this period, if the temperature increases above 77'F, be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

MILLSTONE - UNIT 3 3/4 7-13 Amendment No.

-0278 I