%Qfy Florida Power C O m P O n A T e 0.s June 24,1983 3F-0683-13 Mr. H. R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555

Subject:

Crystal River Unit 3 Docket No. 50-302 Operating License No. Otf-72 Request No.109

Dear Mr. Denton:

Enclosed are three (3) originals and forty (40) copies of Request No.109 requesting amendment to Appendix A of Operating Licence No. DPR-72. As part of this request, the proposed pages are enclosed.

This amendment will allow Florida Power Corporation to take compensatory action other than the cstablishment of a continuous fire watch when a penetration fire barrier is found to be non-functional.

Florida Power Corporation considers this amendment not likely to involve a Significant Hazard Consideration. Additionally Florida Power Corporation requests that this amendment be granted as soon as possible consistent with exigent change requests. Currently approximately 34 persons per day are required to maintain the continuous fire watch at a cost of $100,000 per month. This appears excessive in comparison to the cost of an hourly fire watch (approximately $3,000/ month).

Florida Power Corporation considers Request No.109 to be a Class III Amendment per 10 CFR 170.22 as it involves a single safety issue. Accordingly, a check for four thousand dollars ($4,000) is enclosed.

Since ly, f

G. R. Westafer Manager Nuclear Fuel and Licensing Management PGH/ mig 0

00 DR ADDCK 05ooom 30h ig4'0 8306300225 830624

/

Enclosure p

8 I

cc:

Mr. 3. P. O'Reilly, Regional Administrator Office of Inspection and Enforcement, Region II' U. S. Nuclear Regulatory Commission Suite 2900 101 Marietta St. N.W.503 Atlanta, Georgia 30 General Office 32o1 Thirty fourtn street souin. P.O. Box 14042. st. Petersburg. Florida 33733 813-866-5151

m STATE OF FLORIDA COUNTY OF PINELLAS G. R. Westafer states that he is the Manager, Nuclear Licensing and Fuel Management, of Florida Power Corporation; that he is authorized on the part of said company to sign and file with the Nuclear Regulatory Commission the information attached hereto; and that all such statements made and matters set forth therein are true and correct to the best of his knowledge, information, and belief.

G. R.Testafsr

/

Subscribed and sworn to before me, a Notary Public in and for the State and County above named, this 24th day of June,1983.

tv, [ f/,{ m dtv

' Notary Public Notary Public, State of Florida at Large, My Commission Expires: May 29,1984

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION IN THE MATTER OF

)

)

DOCKET NO. 50-302 FLORIDA POWER CORPORATION )

CERTIFICATE OF SERVICE G. R. Westafer deposes and says that the following has been served on the Designated State Representative and the Chief Executive of Citrus County, Florida, by deposit in the United States mail, addressed as follows:

Chairman, Administrator Board of County Commissioners Radiological Health Services of Citrus County Department of Health and Citrus County Courthouse Rehabilitative Services Inverness, FL 32650 1323 Winewood Blvd.

Tallahassee, FL 32301 One (1) copy of Technical Specification Change Request No. 109 requesting amendment to Appendix A of Operating License No. DPR-72.

FLORIDA POWER CORPORATION G. R. Westafer '

/

Manager Nuclear Licensing and Fuel Management SWORN TO AND SUBSCRIBED BEFORE ME THIS 24th DAY OF JUNE 1983.

Y+(d&f I

ETN

' Nota Public Notary Public, State of Florida at Large My Commission Expires: May 29,1984 (NOTARIAL SEAL)

1 1

FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 DOCKET NO. 50-302/ LICENSE NO. DPR-72 REQUEST NO.109, REVISION O PENETRATION FIRE BARRIERS i

l LICENSE DOCUMENT (S) INVOLVED: Technical Specification, Appendix A PORTION (5): 3.7.12, page 3/4 7-47 NRC REVIEW AND APPROVAL IS REQUIRED PRIOR TO IMPLEMENTATION.

REGULATORY BASIS: 10 CFR 50.59, Change to Technical Specifications DESCRIPTION OF REQUEST:

Change the ACTION statement and Bases Section of the Penetration Fire Barriers l

specification to allow compensatory action other than the establishment of a continuous fire watch near the non-functional barrier.

Specifically, the following action should be taken when any of the required fire barrier penetrations are non-functional:

With one or more of the above required fire barrier penetrations non-functional, within one hour either, establish a continuous fire watch on at least one side of i

the affected penetration, or verify the OPERABILITY of fire detectors on at least one side of the non-functional fire barrier and establish an hourly fire watch patrol.

Restore the non-functional fire barrier penetration (s) to functional status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Repcrt to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the non-functional penetration and plans and schedule for restoring the fire barrier penetration (s) to functional status.

REASON FOR REQUEST:

The current specification addressing Penetration Fire Barriers requires establishment of a continuous fire watch when any barrier is non-functional. Other courses of action exist that can be taken to mitigate the consequences of a fire and that will require less expenditure of manpower costs. The availability of another approved course of action will also allow more operational flexibility to determine the most effective action to take.

In a case particular to Crystal River Unit 3, the discovery that installed fire dampers are certified as one and a half hour fire barriers (rather than the required three hours) has lead to the establishment of a large number of fire watches. This is requiring considerably more manpower than would be necessary to maintain a roving fire watch and to verify the operability of the fire detection systems.

EVALUATION OF REQUEST:

The requirement to establish a roving fire watch and verify the operability of fire detection system or establish a continuous fire watch assures that a fire in the affected area is detected early enough to initiate protective actions. This requirement is consistent with NUREG-0103,

Revision 4, Standard Technical Specifications for Babcock and Wilcox Pressurized Water Reactors. Thus, issuance of a license amendment including this requirement will not:

(1)

Involve a significant increase in the probability or consequence of an accident previously evaluated; or (2)

Create the probability of a new or different kind of accident from any accident previously evaluated; or (3)

Involve a significant reduction in a margin of safety.

REFERENCES:

NUREG-0103, Rev. 4, Standard Technical Specifications for Babcock & Wilcox Pressurized Water Reactors, page 3/4 7-41.

NUREG-0800, Standard Review Plan', Section 9.5.1-7, pp. 9.5.1 52.

10 CFR 50.91 (b) e 7

s 1

~

s a

t NO SIGNIFICANT HAZARDS CONSIDERATION DETERMINATION

.\\

Docket No:

30-302/ License No. DPR-72 Facility:

Crystal River Unit J t

Date of Application: June.24,,1983 Licensee:

Florida Power Corporation 1

- s e

~

Request for: Issuance of Request No.109 3

This request changes the compensatory action requirements addressing non-functional fire barrier penetrations to ayos establishment of a roving fire watch and verificatioriof fire detection system.coerability irilieu of the establishment of a continuous fire watch.

m s

Significant Hazards Consideration Determination:

sN i (x)

Amendment involves no significant hazards cons'iderations.

(

)

Amendment involves significant hazards considerations.

,s s

q Basis for Determination:

This change is consistent with 'the StafI's recommendations concerning fire barrier penetrations published in NUREG-0103, Revision 4, Standard Technical Specifications for Babcock and Wilcox ' Pressurized Water Reactors and is consistent with fae acceptance criteria in the Standard Review Plan. Therefore, tiiis amendment is similar with the examples given in FR 14864 as typically not including a significqnt hazards consideration.

i s

Requested Implementation Date:

l l

Florida Power Corporation requests this, amendment tie granted as soon as possible consistent with exigent change requests; An evaluation has indicated that the resources that are necessary to provide compensatory action could be greatly decreased without a l:

significant reduction in safety. Currently approximately 34 persons per day are required to maintain the continuous fire watch at a cost of approximately $100,000 per month.

This appears excessive in comparison to the cost of an hourly roving fire watch (approximately $3,000 per month).