1 s4 TENNESSEE VALLEY AUTHORITY CH ATTANOOGA. TENNESSEE 37401 400 Chestnut Street Tower II c:a w
May 23, 1983 5:
M
.4C p
?%
c$
BLRD-50-438/83-32 a
BLRD-50-439/83-28 E5 Q3 v=
CJ1 C..
W 5"
U.S. Nuclear Regulatory Conrnission Region II Attn:
Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303
Dear Mr. O'Reilly:
BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - CABLE BEND RADII IN GOING FROM VERTICAL TO HORIZONTAL TRAYS - BLRD-50-438/83-32, BLRD-50-439/83 FIRST INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector Linda Watson on April 22, 1983 in accordance with 10 CFR 50.55(e) as NCR 2331. Enclosed is our first interim report. We expect to submit our next report by October 21, 1983 If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.
Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing l
Enclosure cc:
Mr. Richard C. DeYoung, Director (Enclosure)
Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Records Center (Enclosure)
Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 4
T pO 8305310193 830523
-f gDRADOCK 05000438 gg PDR
.y 66 27
/
An Equal Opportunity Employer
4 ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 CABLE BEND RADII IN GOING FROM VERTICAL TO HORIZONTAL TRAYS BLRD-50-438/83-32, BLRD-50-439/83-28 10 CFR 50.55(e)
NCR 2331 FIRST INTERIM REPORT Description of Deficiency TVA construction specification 0-38 requires a minimum bend radius of no less than 19.6 inches for 8kV power cables to prevent overstressing the cable insulation. Some of the cable tray fittings used at Bellefonte require an installed cable bend radius as short as 7 inches.
Interim Progress TVA is contacting the vendor to provide assistance in determining if a 7-inch bend radius will permit acceptable cable performance.