's a-TENNESSEE VALLEY AUTHORITY CH ATTANOOG A. TENNFSSEE 37401 400 Chestnut Street Tower II July 20, 1982 BLRD-50-438/82-20

=

.z BLRD-50-439/82-18 i-2 m

'.l U.S. Nuclear Regulatory Commission

.7 l

i Region IIMr. James P. O'Reilly, Regional Administrator g

Attn:

101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 A!aD P - OMTSSIONS TO AUXILIARY F SECOND INTERIM PUMP DRAWINGS - BLRD-50-438/82-20, BLRD-50-439/82 REPORT The subject deficiency was initially reported to NRC-0IE Inspector 25, 1982 in accordance with 10 CFR 50.55(e) as R. V. Crlenjak on February This was followed by our first interim report dated NCR BLN BLP 8207.

March 25, 1982. Enclosed is our second interim report. We expect to submit our next report by September 8, 1982.

If you have any questicos concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing Enclosure Mr. Richard C. DeYoung, Director (Enclosure) cc:

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 1

g,gesCOM e

'~

8208020104 820720

-[_ [ [ L PDR ADOCK 05003438 An Equal Opportunity Employer S

paa

.f ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS-1 AND 2

_j OMISSIONS TO AUXILIARY FEEDWATER PUMP DRAWINGS NCR BLN BLP 8207 BLRD-50-438/82-20, BLRD-50-439/82-18 10 CFR 50.55(e)

SECOND INTERIM REPORT Description of Deficiency The auxiliary feedwater (AFW) pumps were purchased without vent, drain, and turbine bearing cooling water interconnecting piping.

Connections to the pumps and turbines were supplied by the respective manufacturer with the understanding that TVA would provide the necessary piping design drawings and materials to meet TVA's and the pump specifications. The vents, drains, and turbine bearing cooling water interconnecting piping were not designed.

Interim Progress The auxiliary feedwater pump vents, drains, and turbine bearing cooling water interconnecting piping have been designed and incorporated on design criteria diagram (3BWO618-CA-01) and piping design drawing (3BWO418-CA-04, -08, and -12).

These drawings will be issued by July 30, 1982.

~ -