57)-35$

Colt industries

[g,*,"yf1",'

701 Lawton Avenue bebit. Wisconsin 53511 608/364-4411 February 15, 1983 Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Ill. 60137 Attention: Mr. James G. Keppler, Director, Region III

Subject:

Colt Industries-Fairbanks Morse Engine Division Emergency Diesel Generators Possible Thermostatic Valve Malfunction Fail Safe To " Full Cooling Position" Part 21 Report Supplemental Report No. 4 - Public Service Electric & Gas Co.-Hope Creek Unit #1

References:

May 25, 1982; June 28, 1982 and September 17,1982 Part 21 Reports - Robertshaw Valves - same subject Gentlemen:

The lower overrun assemblies in the Robertshaw valves installed on the Diesel Generator Sets at the Public Service Electric & Gas Co., Hope Creek Unit 1 have been replaced with overrun assemblies utilizing cotter pins to positively lock the nut to the stem.

The units are now free of the reported potential defect.

A copy of this report is being forwarded to the utility involved.

Very truly yours, iarty MANAGER UTILIT SALES JMM:jc cc: Bechtel Power Corp.

P. O. Box 3965 San Francisco, CA 94119 Attention: Hope Creek Project Engineer U. S. Nuclear Regulatory Commission c/o Document Management Branch Washington, D.C.

20555 Robertshaw Controls Company P. O. Box 400 Knoxville, TN 37901 Attention:

T. T. Howell, Quality Mgr.

8302250201 830215 PDR ADOCK 05000354 FEB 1 % 1983 S

PDR f /f