ML20070U786

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Weld Defects on 24 Mitered Joints on 12 Header Supports Used on Reactor Bldg Cooler Coils. Initially Reported on 820621.Supports Returned to Manufacturer.Also Reported Per Part 21
ML20070U786
Person / Time
Site: Bellefonte 
Issue date: 02/03/1983
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21-83 10CFR-050.55E, 10CFR-50.55E, NCR-1853, NUDOCS 8302140018
Download: ML20070U786 (2)


Text

e TENNESSEE VALLEY AUTHORITY CH ATTANOOGA. TENNESSEE 37401 400 Chest'ut Street Tower II February 3, 1983 BLRD-50-438/82-46 u

m rn U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator p

101 Marietta Street, Suite 3100 E5 Atlanta, Georgia 30303 G

Dear Mr. O'Reilly:

B BELLEFONTE NUCLEAR PLANT UNIT 1 - WELD DEFECTS ON REACTOR BUILDING

~

COOLER SUPPORTS - BLRD-50-438/82 FINAL REPORT The subject deficiency was initially reported to NRC-0IE Inspector R. V. Crlenjak on June 21, 1982 in accordance with 10 CFR 50.55(e) as NCR 1853 This was followed by our interim reports dated July 20, and October 27, 1982. Enclosed is our final report. We consider 10 CFR Part 21 applicable to this deficiency.

If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY DS W

%L.M. Mills, Manager l

Nuclear Licensing l

Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement l

l U.S. Nuclear Regulatory Commission l

Washington, D.C.

20555 l

CUk i

8302140018 830203 101 4 DR ADOCK 05000

-h '

e dI~

f l

An Equal Oooortunity Empfoyer l

ENCLOSURE BELLEFONTE NUCLEAR PLANT UNIT 1 WELD DEFECTS ON REACTOR BUILDING COOLER SUPPORTS NCR 1853 BLRD-50-438/82-46 10 CFR 50.55(e)

FINAL REPORT l

Description of Deficiency Twenty-four mitered joint' on 12 header supports which are used on the Reactor Building (RB) cooler coils exhibit either or both lack of fusion and undercut (greater than 1/32 inch and less than 1/8 inch).

The welds were fabricated by the manufacturer, American Air Filter (AAF)

Company, Incorporated, Louisville, Kentucky, and the units were supplied to TVA under the NSSS contract awarded to Babcock & Wilcox (B&W) of Lynchburg, Virginia. The AAF drawings specify that welding shall conform to the AWS Code D1.1, Revision 2, dated 1974.

Safety Implications Should the subject welds fail, the RB coolers could experience a loss-of-function failure. The RB coolers are used during both normal operations and accident conditions as a primary safety-related component to prevent containment overpressurization and/or overheating of the RB atmosphere.

Consequently, the cited deficient welds could contribute to a condition adverse to the safety of operations of the p? ant.

Corrective Action The subject supports were returned to AAF. A joint inspection of the supports was performed there by representatives from TVA Construction, TVA Engineering Design (EN DES), and AAF and all parties have agreed upon the specific weld defects to b_ repaired. After the weld repairs have been completed, an inspector from EN DES's Quality Engineering Branch (QEB) will l

reinspect all the repaired areas at AAF's shop to verify that the welds now conform to the requirements of AWS Code D1.1, revision 2, dated 1974, as specified on the AAF drawings. AAF will prepare a weld map to document the repairs made for each support. A copy of the weld map will be included when the supports are returned to the Bellefonte site. Final acceptsnce of the reworked supports will be documented on the NCR upon site inspection t

and acceptance. Corrective actions are scheduled for completion by March 28, 1983

^ ~

To prevent recurrence, GEB has informed the responsible TVA regional quality control office of this nonconforming condition and requested that they increase their source surveillance on all future shipments from any of AAF's manufacturing facilities.