Proposed Tech Specs Requesting That Surveillance Requirement SR 4.8.1.1.2.d in Note to Table 4.8-1 Be Renumbered as SR 4.8.1.1.2.f
ML20070S201
Person / Time
Site: Summer 
Issue date: 03/27/1991
From:
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
Shared Package
ML20070S192 List:
References
NUDOCS 9104020191
Download: ML20070S201 (2)


Text

. _ _.... _ _ _.

i i

ATTACHMENT MARKE0-UP TECHNICAL SPECIFICATION PAGES Pace SDecification Chance Description 3/4 8-7 Table 4.8-1 Renumber the referenced SR 4.8.1.1.2.d to SR 4.8.1.1.2.f l

9104020191 910327 PDR ADOCK 03000393 P

pop

=

\\

TABLE 4. Sol 0!ESEL GENERATOR TEST SCHEDULE J

Number of Failures Number of Failures in in Last 100 Valid Last 20 Valid Tests

  • Tests
  • Test Frequency

$1 34 Once per 31 days 12**

15 Once per 7 days l

1

  • Criteria for determining number of-failures and number of valid tests shall be in eccordance with Regulatory Position C.2.e of Regulatory Guide 1.108, but determined on a per ciesel generator basis.

For the purposes of determining the requireo test frequency, the previous test failure count may be reduced to zero if, in conjunction with the manu-f acturer a complete diesel overhaul to like new conditions is completed, and if acceptable reliability has been demonstrated.

The reliability crite-rion shall be the successful completion of 14 consecutive tests in a single series.

Ten of these tests shall be in accordance with Surveillance Require-ment a.8.1.1.2.a.3 and 4.8.1.1.2.a,4; four tests, in accordance with Surveillance Requirement:4.0.1 1 If this criterion is not satisfied Ya I l' 2

  • I during the TirstWi~eror tesks.2.d., any alternate criterion to be used to transvalue the failure count to zero requires NRC approval.
    • The assoc'ated test f requency shall be maintained until seven consecutive f ailure f ree demands have been performed and the number of f ailures in the

~

last 'O valie demands has been reduced to one.

4 r

l SUMM(R UNIT 1-3/4 8 7 AMENDMENT NO J