ML20070Q334

From kanterella
Jump to navigation Jump to search
First Interim Deficiency Rept Re Uncontrolled Parts for Battery Chargers from Power Conversion Products,Inc. Initially Reported on 821217.Drawing Error Suspected.Next Rept Expected by 830422.Also Reportable Per Part 21
ML20070Q334
Person / Time
Site: Bellefonte 
Issue date: 01/17/1983
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21-83 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8301260459
Download: ML20070Q334 (1)


Text

.. _

e_

e 4

TENNESSEE VALLEY AUTHORITY CH ATTANOOGA. TENNFSSEE 374oi 400 Chestnut Street Tower II Jaba'/YI 17, 1983; 2b i

BLRD-50-438/83-05 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNIT 1 - UNCONTROLLED PARTS FOR BATTERY CHARGERS BLRD-50-438/83 FIRST FROM POWER CONVERSION PRODUCTS, INC.

INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector L. Watson on December 17, 1982 in accordance with 10 CFR 50.55(o) as NCR BL-2-P.

Enclosed is our first interim report. We expect to submit our next report on or about April 22, 1983 We consider 10 CFR Part 21 applicable to this deficiency.

If you have any questions concerning this matter, please get in touch ifith R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing Enclosure l

cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement j'

U.S. Nuclear Regulatory Commission Washington, D.C.

20555 l

t l

l ThhtICIAT N M 8301260459 830117 PDR ADOCK 05000438 e

d l

l S

PDR

!- [ O f l

An Equal Opportunity Employer

{

h * '..

ENCLOSURE BELLEFONTE NUCLEAR PLANT UNIT 1 UNCONTROLLED PARTS FOR BATTERY CHARGERS FROM POWER CONVERSION PRODUCTS, INC.

NCR BL-2-P BLRD-50-438/83-05 10 CFR 50.55(e)

FIRST INTERIM REPORT Description of Deficiency Amplifier boarca (replacement parts) purchased for the Class IE 125V de battery obergers were ordered by vendor part number from Power Conversion Products, Ind). (PCP), Charlotts, North Carolina. The same part number is also comon to the non-Class IE 24V do, 48V do, and 125V do battery chargers; however, the amplifier boards are actually modified by the vendor for use in each respective type of charger.

The failure of the vendor te identify the differences between the amplifie.a boards caused the wrong amplifier board to be placed in the Class IE 125V de battery charger, thus resulting in erratic operation of the charger.

Interim Progress.

  • 1VA has contacted PCP and they have stated that the problem is nothing more than a drawing error and will confim this by telex. TVA is awaiting the telex from PCP to determine if this problem is an isolated occurrence or is generic in nature.
3. -

's l i

i

=

l l

i w.

m o. ws. :

7

.. ~.

. _ -... _.. _