ML20069H622

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Untimely Reinsp of 3,069 safety- Related Pipe Hanger Welds.Initially Reported on 820908. Contractor Will Inspect Hanger Supports Installed Before June 1981 Prior to Fuel Load
ML20069H622
Person / Time
Site: Braidwood  Constellation icon.png
Issue date: 10/13/1982
From: Tramm T
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, 5204N, 82-08, 82-8, NUDOCS 8210190662
Download: ML20069H622 (2)


Text

'

Commonwealth Edison g

i One First Nation ~l PI:2a Chic go, Ilhnois

~ Addr:ss R: ply to: Post Offics Box 767 Chicago, Illinois 60690 l

October 13, 1982 Mr. James G. Keppler, Regional Administrator Directorate of Inspection and Enforcement - Region III U. S. Nuclear Regulatory Co mmission 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Braidwood Station Units 1 and 2 Pipe Support Assembly Inspections NRC Do cket No s. 50-456 and 457

Dear Mr. Keppler:

On September 8, 1982 Commonwealth Edison Company notified Mr. D.

Hayes of your office a deficiency reportable pursuant to 10 CFR 50.55(e) regarding inspection of welds in piping supports at Braidwood Station.

This letter fulfills the 30-day reporting requirement.

For your tracking purposes this deficiency is numbered 82-08.

Description o f De ficiency Originally, only NF safety related pipe hangers were undergoing weld inspection at the time of installation.

Hange r configuration was to be checked at the time of turnover for test when the system was walked down.

In June 1980 construction practices were improved to include dimensional checks and weld inspections on all NF safety related hangers.

In June 1981 construction practices were revised to require these inspections on all safety related hangers.

In September 1982 we determined that reinspection o f 3069 hangers installed prior to June 1981 was not proceeding at a satisfactory pace.

This was reported because of the extensive inspection program required to meet the standards of our upgraded construction practice.

Analysis of Safety In plica tion s The original inspection program provided reasonable assurance of pipe support adequacy.

The improved inspection program provides better assurance but does not improve safety in a manner which can be readily assessed.

Corrective Action Taken To conform to the latest requirements, the contractor will inspect the 3069 safety related supports installed prior to June, 1981 in accordance with QC Procedure B23, to assure that the hanger assembly, configuration, and welding is in accordance with the design drawing.

This work will proceed cincurrent with installation of other hangers and will be completed prior to fuel load.

OhhoO4j6 0CT 1

^

8

n

. -i' 2--